USER MANUAL ā Release 1.2 of 01/01/2010 Page 163 of 191
57.12 COLD SIDE FLOW SWITCH ALARM (DIFFERENTIAL PRESSURE SWITCH)
AEFL (evaporator side flow switch alarm)
(the flow switch alarm is only active in the units configured as air/water -
water/water)
ID active for the AL16 time from water pump start-up, after ID active for AL18
time
ID not active for the time AL19
Automatic ā it becomes manual if ID active for time AL17 counted from the
expiry of AL18 (reset procedure in functions menu)
Alarm + buzzer relays only activated if the flow switch alarm is activated in
normal working phase
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
It follows its regulation
It follows its regulation
Free-cooling on/off valve
It follows its regulation
Anti-freeze/Support/boiler
It follows its regulation
It follows its regulation
With PA1=1 always on; off when the alarm becomes manual reset
With PA1=2 follows its regulation; off when the alarm becomes manual reset
It follows its regulation