57. ALARMS
The alarm codes and signals are made up from letters and numbers that identify the different types.
Types of alarm:
Letter A = unit alarm
Letter B = circuit alarm
Letter C = compressor alarm
57.1 COMPRESSORS BLOCK ALARMS
If the compressors are OFF for:
Temperature control
Stand by
Remote OFF
if AL30 = 0 the following alarms are ignored:
! Thermal overolad compressors 1 to 16
if AL15 = 0 the following alarms are ignored:
Oil low pressare / low level compressors 1 to 16
AL30
Compressor thermal overload alarm detection with compressor
OFF
0 = Disabled
1 = Enabled
0
1
AL15
Oil low pressure / low level alarm enabling with compressor OFF
0
1