EasyManua.ls Logo

dIXEL IPC400D SERIES - Condensation Fan Circuit Breaker Alarm

dIXEL IPC400D SERIES
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
!
USER MANUALRelease 1.2 of 01/01/2010 Page 170 of 191
Version: 02/03/2010
The alarm remains in stand-by, OFF remote or with compressor off due to temperature control only if it was
present before and with MANUAL reset.
57.20 CONDENSATION FAN CIRCUIT BREAKER ALARM
Display label meaning
b1tF (circuit n° 1 condensation ventilation circuit breaker alarm)
b2tF (circuit n° 2 condensation ventilation circuit breaker alarm)
b3tF (circuit n° 3 condensation ventilation circuit breaker alarm)
b4tF (circuit n° 4 condensation ventilation circuit breaker alarm)
Cause of activation
With configured circuit ID active
Warning: if an ID is configured as common condensation circuit breaker, the
identification labels are displayed together)
Reset
With ID not active
Reset
Manual. (reset procedure in functions menu)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
it follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
it follows its regulation
Idle running valve
It follows its regulation
Supply ventilation
Off
Condensation ventilation
Off
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Compressors
Off
Pump down solenoid valve
off

Table of Contents