57.14 SUPPLY FAN CIRCUIT BREAKER ALARM
Display label meaning
AtSF (Flow fan circuit breaker alarm)
Cause of activation
If CF01 = 0 with ID active
On fan start-up, the alarm is ignored for time AL16
Reset
ID not active
Reset
Always manual
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Reverse valve
it follows its regulation
Recovery valve
it follows its regulation
Free-cooling on/off valve
it follows its regulation
Auxiliary relay
it follows its regulation
Idle running valve
it follows its regulation
Supply ventilation
off
Condensation ventilation
off
Support/boiler/anti-freeze
off
Pump/and water evaporator
and condenser
off
Compressors
off
Pump down solenoid valve
off
SUPPLY FAN ALARM MANUAL RESET
It is necessary to enter the functions menu (reset procedure in flashing rSt label functions menu if the alarm
is not active from AL19, otherwise NO label). Press set to reset the alarm. The signal disappears. If
managed, the supply fan can start and the alarm is by-passed for AL16 allowing the regular start-up of the
unit if the alarm is not present during this period of time.