USER MANUAL – Release 1.2 of 01/01/2010 Page 167 of 191
57.15 DOMESTIC HOT WATER PUMP FLOW SWITCH ALARM
AHFL (domestic hot water pump flow switch alarm)
(the flow switch alarm is only active with FS01 ! 0)
ID active for the AL16 time from water pump start-up, after ID active for AL18
time
ID not active for the time AL19
Automatic – it becomes manual if ID active for time AL17 counted from the
expiry of AL18 (reset procedure in functions menu)
Alarm + buzzer relays only activated if the flow switch alarm is activated in
normal working phase
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
Off when the alarm becomes with manual reset
Production of domestic hot
water function
They follow their regulation
57.16 DOMESTIC SOLAR PANELS WATER PUMP FLOW SWITCH ALARM
APFL (solar panels pump flow switch alarm)
(the flow switch alarm is only active with FS01 ! 0)
ID active for the AL16 time from water pump start-up, after ID active for AL18
time
ID not active for the time AL19
Automatic – it becomes manual if ID active for time AL17 counted from the
expiry of AL18 (reset procedure in functions menu)
Alarm + buzzer relays only activated if the flow switch alarm is activated in
normal working phase
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
Off when the alarm becomes with manual reset
They follow their regulation