EasyManua.ls Logo

dIXEL IPC400D SERIES - IPROEX60 D Expansion Module; Expansion Module LEDs Meaning;Working

dIXEL IPC400D SERIES
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
!
USER MANUALRelease 1.2 of 01/01/2010 Page 56 of 191
Version: 02/03/2010
8. IPROEX60D EXPANSION MODULE
The following can be connected to the programmable devices of the iPro.CHILL range: the IPROEX60D
expansion module to ease the increase of I/O available to the user.
Up to 4 expansion modules IPROEX60D can be connected to the iPro.CHILL for increasing the I/O number.
Their address must be between 5 (Expansion module number 1) to 8 (expansion module number 4) and
must be consecutive, that is if 2 modules are configured they must have addresses 5 and 6.
8.1 EXPANSION MODULE LEDS MEANING/WORKING
The following table gives the working mode of the LEDs
LED
MODE
MEANING
PWR ON
On
Module powered
ALARM
On fixed
Indicates the presence of a general alarm situation
TX/RX CANBus
Flashing
Communication active
TX/RX CANBus
Fixed