57.13 HOT SIDE FLOW SWITCH ALARM (DIFFERENTIAL PRESSURE SWITCH)
ACFL (Condenser side flow switch alarm)
(the flow switch alarm is only active in the units configured as air/water -
water/water)
ID active for the AL22 time from water pump start-up (alarm by-pass time),
after ID active for AL24 time
alarm disabled if AL21=0
Alarm only enabled in cooling working mode if AL21=1
Alarm only enabled in heating working mode if AL21=2
Alarm enabled in cooling and heating working mode if AL21=3
ID not active for the time AL25
Automatic ā it becomes manual if ID remains active for time AL23 counted
from the expiry of AL24 (reset procedure in functions menu)
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
Relay + buzzer only activated if the flow switch alarm is activated in normal
working phase
It follows its regulation
It follows its regulation
Free-cooling on/off valve
It follows its regulation
Anti-freeze/Support/boiler
It follows its regulation
It follows its regulation
With PA17=1 always on; off when the alarm becomes manual reset
With PA17=2 follows its regulation; off when the alarm becomes manual reset
It follows its regulation
WARNING
Relay + buzzer are only activated if the flow switch alarm is activated in normal working phase.