52.2 HEAT RECOVERY SIDE PRIORITY
rC02 = 1 Heat recovery side priority
Heat recovery working mode is obtained only if the unit is in cooling mode on call of the recovery
temperature control.
In this case compressor switch-on/off refers to the condenser probes, therefore hot water is obtained (heat
recovery working mode) even without a request for cold water.
DISABLING/ENABLING OF HEAT RECOVERY WORKING DUE TO CONDENSATION
PRESSURE/TEMPERATURE
The heat recovery mode is disabled to allow the unit to function in cooling plus recovery mode to prevent a
possible high pressure intervention Disabling of the heat recovery working mode is managed via the
analogue input configured as circuit condensation probe (according to the value set in the Par CF07=0
temperature control or CF07= 1 pressure control).
WORKING
DISABLING OF HEAT RECOVERY
With the heat recovery working state selected due to temperature control compressors switch-on request, if
the condensation pressure/temperature is the same as or exceeds the set rC06 = heat recovery function
disabling set, the heat recovery function is activated in the circuit to which the transducer/NTC probe belong.
ENABLING OF HEAT RECOVERY
If the condensation temperature or pressure drops below the set rC06 = heat recovery disabling set the
differential rC07= heat recovery enabling differential the heat recovery function is enabled in the circuit to
which the transducer/NTC probe belong.
NOTES HEAT RECOVERY ENABLING DISABLING
To prevent prolonged working in heat recovery disabling with temperature/pressure conditions between
deactivation set and activation differential, when the condensation temperature/pressure is below the set
rC06 the time set in the Par. rC08= Maximum heat recovery disabling time due to condensation
pressure/temperature is counted. When this time expires the heat recovery function is enabled even if the
temperature has not dropped below the rC06 set the rC07 differential.
CONDENSATION FAN MANAGEMENT IN HEAT RECOVERY MODE
The working of the relay outputs or ventilation control proportional depend on the parameter rC09 = 0. The
fans are always enabled with working in heat recovery mode.
rC09 = 1 unit with 1 circuit and 1 row of fans (FA05 = 0):
the fans output is disabled in heat recovery mode
rC09 = 1 unit with several circuits and 1 row of fans (FA05 = 0):
with heat recovery working of just one circuit the fans output is managed by the transducer/condensation
probe of the circuit that is not recovering
the fans output is disabled with heat recovery working of both circuits
rC09 = 1 unit with several separate ventilation circuits (FA05 = 1):
the relative fans output is disabled in heat recovery working mode
the fans outlet is enabled if:
there is no heat recovery call
the threshold of parameter rC6 is exceeded (to prevent the high pressure intervention).