EasyManua.ls Logo

dIXEL IPC400D SERIES User Manual

dIXEL IPC400D SERIES
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
!
USER MANUALRelease 1.2 of 01/01/2010 Page 1 of 191
Version: 02/03/2010
PROGRAMMABLE CONTROLLERS
IPC400D SERIES
USER MANUAL
"#$%&

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the dIXEL IPC400D SERIES and is the answer not in the manual?

dIXEL IPC400D SERIES Specifications

General IconGeneral
BranddIXEL
ModelIPC400D SERIES
CategoryController
LanguageEnglish

Summary

General Recommendations

Safety Precautions

Essential safety guidelines for operating the device, including power checks and maintenance warnings.

Generalities

Main Functions

Overview of the controller's primary operational capabilities, supporting various unit types and functions.

IPC400D Series Features

Analogue - Digital Inputs/Outputs Configurations

ID1 – ID20 Digital Inputs Configuration

Explains the configuration options for digital inputs, mapping specific functions to input terminals.

RL1- RL15 Digital Outputs Configuration

Details the configuration settings for digital outputs, assigning functions to relay terminals.

Analogue Inputs PB1 - PB10 Configuration

Covers the configuration of analogue inputs, specifying probe types and voltage/current ranges.

Configuration of the OUT1 / OUT4 Proportional Outputs

Describes how to configure proportional outputs for circuits 1 through 4, including 0-10V signals.

Configuration of the OUT5 / OUT6 Proportional Outputs

Explains the configuration for proportional outputs 5 and 6, supporting 4-20mA and PWM signals.

How to Configure the Inputs and Outputs (File IO.CONF)

Guides on configuring inputs/outputs using the IO.CONF file structure and syntax.

Further Connections

Lists and describes additional connection options such as USB, Network, and RS485.

Parameters in Table Form

iPro.CHILL Programmable Controller

IPRO Range Controller LEDs Meaning/Working

Explains the function and status indicated by the controller's various LEDs.

iPro.CHILL Wiring Diagrams

IPC410D Model Hardware Resources

Details the hardware resources and connectivity options for the IPC410D model.

IPC415D Model Hardware Resources

Outlines the hardware resources and connection terminals for the IPC415D model.

NTC/PTC Probes Analogue Inputs

Illustrates the wiring for NTC and PTC analogue inputs, showing common probe terminals.

Digital Inputs

Shows the wiring diagram for digital inputs, indicating common input connections.

4÷20mA Pressure Transducers Analogue Inputs

Provides wiring details for analogue inputs used with 4-20mA pressure transducers.

0÷5V Ratiometric Pressure Transducers Analogue Inputs

Illustrates the wiring for analogue inputs supporting 0-5V pressure transducers.

Outdoor Fan Speed Control PWM Outputs

Explains the wiring for PWM outputs used for outdoor fan speed control.

Outdoor Fan Speed 0÷10V / 4÷20mA Outputs

Details wiring for 0-10V or 4-20mA outputs to control outdoor fan speed.

Servomotors Control 0÷10V / 4÷20mA Proportional Outputs

Shows wiring for servomotor control using proportional outputs and signals.

Proportional Outputs Configured for Piloting an External Relay

Describes wiring for proportional outputs used to control external relays.

VGIPC Remote Terminal Collection

Illustrates the connection of VGIPC remote terminals, including wiring and warnings.

IPROEX60D Expansion Module

Expansion Module LEDs Meaning/Working

Explains the meaning of the LEDs on the IPROEX60D expansion module for status indication.

IPROEX60D Expansion Module Wiring Diagrams

IPROEX60D Expansion Model Hardware Resources

Details the hardware specifications and I/O capabilities of the IPROEX60D expansion module.

Expansion Module Connection to the Programmable Unit

Guides on connecting the expansion module to the programmable unit using CANBus and DIP switches.

Electronic Thermostatic Valve Management Driver

Driver Module LEDs Meaning/Working

Explains the status indicated by the LEDs on the XEV20D driver module.

Unipolar/Bipolar Valves Driver Connection Mode

Provides tables for connecting unipolar and bipolar motorized valve bodies from different manufacturers.

XEV20D Electronic Thermostatic Driver Wiring Diagrams

XEV20D Driver Model Hardware Resources

Details the hardware resources and input/output capabilities of the XEV20D driver module.

XEV20D Driver Module Connection to the Programmable Unit

Illustrates the connection of XEV20D driver modules to the programmable unit via CANBus.

NTC / PTC / PT1000 Probe Analogue Inputs

Shows the wiring diagrams for connecting NTC, PTC, and PT1000 probes to the driver.

0÷5V Ratiometric Pressure Transducers Analogue Inputs

Illustrates the wiring for 0-5V pressure transducer analogue inputs.

4÷20mA Pressure Transducers Analogue Inputs

Shows the wiring for 4-20mA pressure transducer analogue inputs.

RS485 Serial Communication Peripherals Connection

RS485 Serial Line

Explains the RS485 serial line, connection recommendations, and cable requirements.

RS485 Master Serial Output Connection with Modbus Protocol

Details how to connect RS485 Master output with Modbus protocol for device communication.

RS485 Slave Serial Output Connection with Modbus Protocol

Describes connecting RS485 Slave output with Modbus protocol for supervision systems.

Remote Connection Via Modem

PC Connection from Remote via Serial or External GSM Modem

Guides on connecting a PC remotely using serial or GSM modems, including warnings.

PC Connection from Remote via Internal Serial Modem

Explains how to connect a PC remotely using the unit's internal serial modem.

Connection to the iPro.CHILL via the Network Port

Local Connection to the PC

Details connecting a PC locally via the network port using a crossover cable.

Connection via Intranet

Explains how to access the controller via an intranet network, requiring IP assignment.

Connection via Internet

Guides on connecting via the internet, requiring a static IP and router configuration.

Using the USB Port

USB Port (Host)

Describes how to use the USB port for downloading applications and uploading parameter maps.

User Interface

How to Modify the Information Present in the Main Screen

Explains how to set time, date, and modify displayed information on the main screen.

Unit Switch-On in Conditioning or Heating Mode

Details how to switch the unit on and off in cooling or heating modes, and status indicators.

Set Key

Guides on using the SET key to adjust set-points for cooling and heating modes.

Probes Key

Explains how to view circuit variables and probe data using the PROBES key.

Alarm Key

Describes how to view and reset alarms, including different alarm states and password protection.

Circ Key

Explains how to monitor circuit status, compressor activity, and condensation/evaporation pressures.

Service Key

Provides access to system parameters, compressor status, pump info, alarms, and diagnostics.

Selection – Working Mode – Enabling – Switch-On – Unit Switch Off

Unit Switch-On/Off from the Keyboard

Explains how to switch the unit on and off using the keyboard interface.

Unit Switch-On/Off from Digital Input

Details controlling unit switch-on/off via a digital input configured for remote operation.

Selecting the Working Mode: Cooling – Heating

Describes how to select and enable the unit's working mode between cooling and heating.

Change Over Function

Explains the conditions and operation for automatic changeover between cooling and heating modes.

Cooling – Heating Mode Selection from Keyboard

Details mode selection via keyboard input based on parameter SP06.

Cooling – Heating Working Mode Selection from Analogue Input

Explains mode selection using analogue input based on external temperature and parameters.

Working with RTC

Working with Clock Disabling Digital Input

Describes operation using a clock disabling digital input for time-based control.

Working with “Ventilation Only” Digital Input (AIR-AIR Unit Only)

Explains ventilation-only operation for AIR-AIR units via a digital input.

Working with Unit in OFF from RTC if ON is Forced from Key

Covers unit operation from RTC when forced ON via a key, with time limits.

Condensing Unit Working Mode

Working with Digital Input Configured as Temperature Control Request

Explains how temperature control requests via digital input manage cooling/heating modes and steps.

Working with Digital Input Configured as Cooling Request

Details how a cooling request digital input manages cooling mode and steps.

Working with Digital Input Configured as Heating Request

Explains how a heating request digital input manages heating mode and steps.

Compressors Temperature Control

Compressor Temperature Control in Cooling Mode

Defines the probe used for unit temperature control in cooling mode via parameter ST09.

Compressor Temperature Control in Heating Mode

Specifies the probe for unit temperature control in heating mode using parameter ST10.

Temperature Control on Two Independent Circuits

Explains how parameter ST12 enables independent temperature control for circuits 1 and 2.

Choice of the Type of Temperature Control

Compressors Proportional Temperature Control Graphics (Unit)

Shows graphical representation of compressor regulation in cooling mode.

Circuit N° 2 Compressors Proportional Temperature Control Graphics

Displays compressor regulation graphics for Circuit 2 in cooling and heating modes.

Compressors Neutral Zone Temperature Control Graphics

Illustrates compressor regulation graphics for neutral zone temperature control.

Working Description

Explains the working principle of compressors within neutral and activation/disabling zones.

Notes Compressors Temperature Control Working

Dynamic Set-Point Function

Dynamic Set-Point Working Graphics

Shows graphical representations of how the dynamic set-point function works with analogue inputs.

Energy Saving from ID Function

Energy Saving Function and Timed Switch-On and Switch-Off

Enables the Daily/Weekly Working in Energy Saving and Automatic Switch On/Off Mode

Guides on programming daily/weekly schedules for energy saving and auto switch-on/off.

Compressors Temperature Control Rotation Control

Fixed Sequence in Selection of the Circuits

Explains fixed sequence selection for circuits, including switch-on and switch-off logic.

Fixed Sequence Inside the Circuit

Describes fixed sequence selection within a circuit for compressor switch-on and off.

Compressor FIFO Rotation

Details the FIFO logic for managing compressor start-up and stop within a circuit.

Circuit FIFO Rotation

Explains the FIFO logic for managing circuit start-up and stop.

Selection of the Circuit for Balancing

Describes criteria for selecting circuits for balancing based on resource engagement and working hours.

Selection of the Compressor for Balancing

Explains compressor balancing criteria, applicable for partialised compressors.

Selection of the Circuit for Saturation

Outlines circuit selection criteria for saturation based on resource engagement and working hours.

Selection of the Compressor for Saturation

Details compressor selection for saturation, applicable with partialised compressors.

Selection of Compressors in the Circuit on the Basis of "Compressor Weight"

Explains selecting compressors based on weight for minimum power increase or working hours.

Selection of the Circuit on the Basis of "Compressor Weight" (Not Available Function)

Describes circuit selection based on compressor weight, noting it's a non-available function.

Compressors Switch-On

Description of Direct Start-Up

Describes direct start-up method for compressors, suitable for various types and sizes.

Direct Start-Up

Details the wiring and configuration for direct compressor start-up using relay outputs.

Direct Start-Up of a Partialised Compressor

Explains direct start-up for partialised compressors, including solenoid control.

Description of Part Winding Start-Up

Describes part winding start-up, used for medium-large compressors to reduce current draw.

Part Winding Start-Up of a Compressor

Details the sequence and relay configuration for part winding start-up.

Part Winding Start-Up of a Compressor/s with 1 or More Partialisations

Explains start-up for partialised compressors using part winding, including solenoid activation.

Description of Star Delta Start-Up

Describes star delta start-up, used for large dimension compressors to reduce peak current.

Star Delta Start-Up of a Compressor

Details the relay configuration and sequence for star delta start-up of compressors.

Star Delta Start-Up of a Partialised Compressor

Explains star delta start-up for partialised compressors, including solenoid and relay activation.

Partialisations Working

Start-Up with Partialised Compressor / Idle Start-Up

Explains enabling minimum capacity working based on compressor type and parameters like CO09.

Gas By-Pass Valve Function on Compressor Start-Up

Describes managing gas by-pass valves for compressor idle start-up.

Intermittent Valve Function for Screw Compressors

Explains intermittent valve function for screw compressors, especially for systems with high thermal inertia.

Compressor Liquid Injection Solenoid Valve Function

Working

Details the working of the liquid injection solenoid valve for compressor protection based on discharge temperature.

Compressor with Inverter Management (Function Not Available)

Management of the Temperature Control of Compressors with Different Cooling Capacity ( Function Not Available)

Compressors in Tandem

Compressors Maintenance Request Function

Evaporator Water Pump Working

Only One Relay Configured as Evaporator Water Pump

Notes that rotation parameters do not affect pump operation when only one relay is configured.

Evaporator Water Pump Rotation

2 Relays Configured as Evaporator Water Pump

Details pump rotation management when two relays are configured for the evaporator water pump.

Rotation of the Evaporator Water Pumps from Digital Input

Explains how pump rotation is managed via digital inputs acting as circuit breakers.

Evaporator Pump Anti-Freeze Management

Water Pump Maintenance Request Function

Supply Fan Working

Supply Fan During Defrost

Discusses stopping the supply fan during defrost for AIR-AIR units to prevent cold air.

Hot Start Function

Enables supply fan start-up only when the condensing coil is sufficiently hot in heating mode.

Function of Supply Fan Maintenance Request

Condenser Water Pump Working

Only One Relay Configured as Condenser Water Pump

Notes that rotation parameters don't affect pump operation if only one relay is configured.

Condenser Water Pump Rotation

2 Relays Configured as Condenser Water Pump

Details pump rotation management when two relays are configured for condenser water pumps.

Rotation of the Condenser Water Pumps from Digital Input

Explains pump rotation management via digital inputs acting as circuit breakers.

Condenser Pump Anti-Freeze Management

Water Pump Maintenance Request Function

Switch-On/Off Working with Pump-Down

Pump-Down Function with Circuit Low Pressure Pressure Switch

Explains pump-down shutdown and start-up using a circuit low-pressure pressure switch.

Pump-Down Function with Dedicated Pressure Switch

Details pump-down function using a dedicated pressure switch for shutdown and start-up.

Pump-Down Function from Analogue Input

Describes pump-down function using an analogue input (low pressure transducer) for shutdown and start-up.

Low Pressure Alarm During the Pump-Down

Explains how parameter AL02 affects low-pressure alarm behavior during pump-down.

Working Examples:

Provides practical examples illustrating pump-down scenarios based on pressure switches and inputs.

Pump-Down Active only in Switch-Off Based on LP Pressure Switch

Example of pump-down on switch-off using LP pressure switch, covering cases with AL02=1 and AL02=2.

Pump-Down Active in Shut-Down and in Re-start, Based on the Analogue Input Relative to the Evaporation Pressure.

Example of pump-down on shut-down/re-start using analogue input for evaporation pressure.

Timed Pump Down Function

Explains managing timed pump-down using parameters PD05 and PD06.

Pump Down Alarm in Start-Up and Stopping

Details managing pump-down alarms in start-up and stopping via Pd parameters.

Circuits Unloading

Unloading from Condensation High Temperature Probe

Explains unloading activation based on condensation high temperature probe readings in cooling/heating.

Unloading from Condensation High Temperature Transducer

Details high pressure unloading function activation and deactivation based on condensation pressure transducer.

Unloading by Low Pressure Transducer

Describes low pressure unloading function, active specifically in heating mode.

Unloading due to Evaporator Water Inlet High Temperature

Manages unloading due to high evaporator water inlet temperature for unit operation and pressure intervention prevention.

Evaporator Water Low Temperature Unloading (No Air-Air)

Used to allow unit function with low evaporator outlet water temperatures to prevent anti-freeze intervention.

Working in Unloading Mode Notes

Provides warnings and notes regarding compressor partialisation and unloading mode behavior.

Condensation Fans Regulator

If the PWM/ 0÷10V Signal Triac Output is Used

Explains parameters FA03, FA04 when PWM/0-10V output is used for proportional fan control.

If the Step Relay Outputs are Used

Details the logic for controlling condensation fans using step relay outputs.

Unique or Separate Condensation

FA05 parameter sets the number of condensation fan sets, allowing unique or separate configurations.

Proportional Fan Regulator Graphics

Graphical representation of proportional fan speed regulation based on pressure/temperature.

Condensation Fan Regulator On / Off in Cooling Mode Graphics

Graphical representation of ON/OFF condensation fan regulation in cooling mode.

Condensation Fan Regulator On / Off in Heating Mode Graphics

Graphical representation of ON/OFF condensation fan regulation in heating mode.

Anti-Freeze/Support Heaters Regulator

Heater Output Working in Cooling or Heating Mode

Ar10 parameter defines anti-freeze heater operation in cooling or heating modes.

Temperature Control in Cooling Mode

Ar06 selects probes for temperature control of anti-freeze heaters in cooling mode.

Temperature Control in Heating Mode

Ar07 selects probes for temperature control of anti-freeze heaters in heating mode.

Temperature Control of the Air/Air Unit Heaters

Depends on relay outputs and NTC probes for controlling AIR/AIR unit heaters.

Support/Anti-Freeze/Boiler Heaters Working Graphics

Shows graphics illustrating support/anti-freeze/boiler heater operation.

Temperature Control of the Evaporator Anti-Freeze Heaters

Details temperature control for evaporator anti-freeze heaters, including defrost cycle behavior.

Temperature Control of the Condenser Anti-Freeze Heaters

Explains temperature control for condenser anti-freeze heaters based on various probe configurations.

Temperature Control of the Boiler Heaters (Anti-Freeze) Boiler Function

Covers boiler heater control for integration/heating and specific cooling uses.

Anti-Freeze Heaters Working from Digital Input

Defrost Function

Description of Defrost Parameters

Provides detailed explanations for all defrost parameters (dF01-dF49).

Defrost with Condensation Fans

Explains defrost activation via condensation fans, including conditions and warnings.

Supply Fan During Defrost

Discusses stopping the supply fan during defrost for AIR-AIR units.

Recovery Function

Heat Recovery Working from Digital Input

Unit with Separate Hydraulic Circuits

Explains heat recovery operation for units with separate hydraulic circuits via digital input.

Unit with Two Parallel Hydraulic Circuits

Details heat recovery operation for units with parallel hydraulic circuits and digital input requests.

Heat Recovery Working by Means of Temperature Probe

User Side Priority

Explains the user-side priority setting (rC02=0) for heat recovery operation.

Heat Recovery Side Priority

Details the heat recovery side priority setting (rC02=1) for operation.

Function for Production of Domestic Hot Water

Management of the Domestic Hot Water Pump

Details managing the domestic hot water pump operation and its timing.

Antilegionella Function

Explains how to activate the antilegionella function using parameter FS12.

Management of the Priority Between the Production of Domestic Hot Water and Water Circuit Utilities

Describes priority management between domestic hot water and water circuit utilities based on FS02.

Solar Panels Water Pump

Explains enabling the solar panels pump based on relay configuration and probes.

Domestic Hot Water Flow Switch and Solar Panels Management

Covers signal and output times for flow switch alarms and solar panels.

Production of Domestic Hot Water with Air/Water Unit, Water/Water in Heating and Common Return Mode: CF01=1,2 - CF02=3 - FS01=1

Details domestic hot water production during winter mode for specific unit configurations.

Domestic Hot Water in Summer Cycle (Only Units with CF02=3)

Explains domestic hot water production during summer cycle for units with CF02=3.

Production of Domestic Hot Water with Air/Water Unit, Water/Water in Heating and Dedicated Return Mode: CF01=1,2 - CF02=3 - FS01=2

Details domestic hot water production during winter mode for specific unit configurations.

Defrost of the Air-Water Units (Only with CF02=2 O CF02=3)

Explains defrost priority over domestic hot water production for AIR-WATER units.

Production of Domestic Hot Water During Working in Summer Cycle (Only Units with CF02 =3)

Details domestic hot water production during summer cycle for units with CF02=3, distinguishing compressor states.

Management of the Refrigerant Load in the Case of Domestic Hot Water Production in the Summer Cycle

Addresses refrigerant load management in summer cycle domestic hot water production to prevent excess refrigerant.

Free Cooling

Resources to be Configured

Lists required analogue inputs, digital outputs, and analogue outputs for free cooling setup.

Free-Cooling with Internal Fan Layout

Shows the layout for free cooling with internal fans, illustrating component connections.

Free-Cooling with External Ventilation Layout

Depicts the layout for free cooling utilizing external ventilation.

Working

Explains the working principle of free cooling, including temperature control and pre-treatment of water.

Free-Cooling Working in Heating Mode

States that free cooling outputs are off in heating mode.

Anti-Freeze Alarm Prevention

Describes the cause, reset, and regulator actions for anti-freeze alarm prevention in free cooling.

Free Cooling Ventilation Working Mode

Explains ventilation regulation modes for free cooling based on FC01 and FC06 parameters.

Fractioned Battery

Details how controls open valves to increase external coil exchange surfaces based on condensation pressure/temperature.

Auxiliary Relay Function

Direct Action Working Enabled

Illustrates the direct action working logic for relays based on set-point and measured value (Pbr).

Reverse Action Working Enabled

Shows the reverse action working logic for relays based on set-point and measured value (Pbr).

Working of the Auxiliary Analogue Outputs (0÷10 Volt)

Alarms

Compressors Block Alarms

Details compressor block alarms ignored based on AL30 and AL15 parameter settings.

Probe Breakdown

Explains probe breakdown alarms, including causes, reset, and regulator actions.

High Pressure Pressure Switch Alarm

Describes high-pressure switch alarms, their causes, reset, and regulator responses.

Compressor Flow High Temperature Alarm from Digital Input

Details compressor high-temperature alarms triggered by digital inputs and their causes.

Low Pressure Pressure Switch Alarm

Covers low-pressure switch alarms, including causes, reset, and regulator behavior.

Oil Float/Pressure Switch Alarm

Explains oil float/pressure switch alarms, their causes, and working oil alarms.

Condensation Temperature/High Pressure Alarm

Describes condensation temperature/high pressure alarms and their impact on regulators.

Low Condensation Temperature/Pressure (If the Low Pressure Transducers are Not Used)

Details low condensation temperature/pressure alarms when low pressure transducers are absent.

Low Evaporation Pressure if the Low Pressure Transducers are Used

Explains low evaporation pressure alarms when low pressure transducers are used.

Air/Air Unit Evaporator/Condenser Air Outlet Low Temperature in Cooling Working Mode Anti-Freeze Alarm

Covers anti-freeze alarms for low air outlet temperatures in cooling mode for AIR/AIR units.

Air/Air Unit Evaporator/Condenser Air Outlet Low Temperature in Heating Working Mode Anti-Freeze Alarm

Details anti-freeze alarms for low air outlet temperatures in heating mode for AIR/AIR units.

Cold Side Flow Switch Alarm (Differential Pressure Switch)

Explains cold side flow switch alarms (differential pressure switch) and their causes.

Hot Side Flow Switch Alarm (Differential Pressure Switch)

Covers hot side flow switch alarms (differential pressure switch) and their causes.

Supply Fan Circuit Breaker Alarm

Describes supply fan circuit breaker alarms and manual reset procedures.

Domestic Hot Water Pump Flow Switch Alarm

Explains domestic hot water pump flow switch alarms and their causes.

Domestic Solar Panels Water Pump Flow Switch Alarm

Covers solar panels water pump flow switch alarms and their causes.

Circuit Breaker Alarm

Details circuit breaker alarms for compressors, including causes and reset procedures.

Discharge Compressors High Temperature Alarm from Analogue Input

Explains high discharge temperature alarms from analogue inputs and their regulator actions.

Evaporator Water Inlet High Temperature Alarm

Covers evaporator water inlet high temperature alarms and their conditions.

Condensation Fan Circuit Breaker Alarm

Describes condensation fan circuit breaker alarms and their regulator actions.

Defrost Alarm

Details defrost alarms, their causes, reset conditions, and regulator behavior.

Unloading Signal Due to High Condensation Temperature/Pressure in Cooling Working Mode

Explains unloading signals due to high condensation temperature/pressure in cooling mode.

Heat Recovery Disabling Signal Due to High Condensation Temperature/Pressure in Cooling Working Mode

Covers heat recovery disabling signals due to high condensation parameters in cooling mode.

Unloading Signal Due to Low Evaporation Pressure in Heating Working Mode

Explains unloading signals due to low evaporation pressure in heating mode.

Unloading Signal Due to Evaporator Water Inlet High Temperature

Details unloading signals due to high evaporator water inlet temperature.

Pump Down Alarm with Low Pressure Pressure Switch/Transducer in Stopping

Explains pump-down alarms related to low-pressure switches/transducers during shutdown.

Pump Down Alarm with Low Pressure Transducer in Start-Up

Covers pump-down alarms related to low-pressure transducers during start-up.

Evaporator Water Pumping Unit Circuit Breaker Alarm

Details evaporator water pump circuit breaker alarms and their causes.

Heat Recovery Condenser Water Pumping Unit Circuit Breaker Alarm

Covers heat recovery condenser water pump circuit breaker alarms.

Unit N. 1 Block General Alarm

Explains the general block alarm for Unit N.1, its causes, and reset procedure.

Unit N. 2 Block General Alarm

Details the general block alarm for Unit N.2, its causes, and reset procedure.

Compressors Maintenance Alarm

Covers compressor maintenance alarms triggered by working hours.

Flow Fan Pumps Maintenance Alarm

Explains maintenance alarms for flow fans and pumps based on working hours.

Condenser Pumps Maintenance Alarm

Details maintenance alarms for condenser pumps triggered by working hours.

RTC Alarm

Covers RTC (Real-Time Clock) alarms indicating clock regulation or breakdown issues.

RTF Alarm

Explains RTF (Real-Time Function) alarms related to clock breakdown.

EEPROM Alarm

Details EEPROM failure alarms, indicating potential data corruption.

Network Frequency Alarm

Covers network frequency alarms when it differs from the configured parameter SP11.

Unit Configuration

Lists various unit configuration error codes (ACF1-ACF17) and their causes.

Remote Terminal Alarm

Describes remote terminal alarms related to connection issues or incorrect HW addresses.

Note: Alarm Relay and Buzzer

Provides notes on how the alarm relay and buzzer function based on alarm presence and reset status.

No Voltage

Automatic to Manual Resrt Alarms Diagnostics