57.23 HEAT RECOVERY DISABLING SIGNAL DUE TO HIGH CONDENSATION
TEMPERATURE/PRESSURE IN COOLING WORKING MODE
b1rC (circuit n° 1 recovery disabling signal)
b2rC (circuit n° 2 recovery disabling signal)
b3rC (circuit n° 3 recovery disabling signal)
b4rC (circuit n° 4 recovery disabling signal)
When working, if the probe configured as condensation temperature or
pressure control measures a value > rC06 set
! of the condensation pressure or temperature measures a value < rc05 set
– rC07 differential
! By heat recovery disabling function inserted after the Par. rC08 time set
Alarm relay + buzzer NOT activated
Relay + buzzer NOT activated
It follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
It follows its regulation
It follows its regulation