USER MANUAL – Release 1.2 of 01/01/2010 Page 174 of 191
57.24 UNLOADING SIGNAL DUE TO LOW EVAPORATION PRESSURE IN HEATING
WORKING MODE
b1Cu (circuit n° 1 unloading from condenser coil signal)
b2Cu (circuit n° 2 unloading from condenser coil signal)
b3Cu (circuit n° 3 unloading from condenser coil signal)
b4Cu (circuit n° 4 unloading from condenser coil signal)
When working, if the probe configured as condensation temperature,
configured as pressure control or as evaporation pressure, measures a value <
Un13 set
! if the condensation pressure/temperature or the evaporation pressure
measures a value > Un13 + Un14
! With unloading function inserted after the time set Par. Un15
Alarm relay + buzzer NOT activated
Relay + buzzer NOT activated
It follows its regulation
it follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
It follows its regulation
It follows its regulation