57.32 COMPRESSORS MAINTENANCE ALARM
Display label meaning
C1MnC16Mn (compressor n° 1…16 maintenance request)
Cause of activation
Compressor working hours > timer set
Reset
Reset working hours (in functions menu)
Reset
Automatic (after the hours reset)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
They follow their regulation
57.33 FLOW FAN PUMPS MAINTENANCE ALARM
Display label meaning
AEP1 (evaporator n° 1 water pump maintenance request)
AEP2 (evaporator support n° 2 water pump maintenance request)
Cause of activation
Water/fan pump working hours >= timer set
Reset
Reset working hours (in functions menu)
Reset
Automatic (after the hours reset)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
They follow their regulation
57.34 CONDENSER PUMPS MAINTENANCE ALARM
Display label meaning
ACP1 (condenser n° 1 water pump maintenance request)
ACP2 (condenser n° 2 water pump maintenance request)
Cause of activation
Condenser water pump working hours >= timer set
Reset
Reset working hours (in functions menu)
Reset
Automatic (after the hours reset)
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
They follow their regulation