USER MANUAL – Release 1.2 of 01/01/2010 Page 176 of 191
57.26 PUMP DOWN ALARM WITH LOW PRESSURE PRESSURE
SWITCH/TRANSDUCER IN STOPPING
b1PH (pump-down alarm in circuit n° 1 shutdown)
b2PH (pump-down alarm in circuit n° 2 shutdown)
b3PH (pump-down alarm in circuit n° 3 shutdown)
b4PH (pump-down alarm in circuit n° 4 shutdown)
With Pd1 ! 0:
! pressure switch: with ID not active and the pump-down ends by time Pd4
! transducer: the set Pd2 is not reached and the pump-down ends by time
Pd4
From pressure switch ID temperature control call not active
From temperature control call with evaporation pressure > Pd2 set + Pd3
differential
Automatic – it becomes manual after Pd7 interventions/hour (reset procedure
in functions menu) It is recorded in the historical alarms only with manual reset
Alarm relay + buzzer activated only when the alarm becomes manual reset
Relay + buzzer activated only when the alarm becomes manual reset
It follows its regulation
it follows its regulation
Free-cooling on/off valve
it follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
It follows its regulation
Support/boiler/anti-freeze
It follows its regulation
Pump/and water evaporator
and condenser
It follows its regulation
Off with manual reset alarm
It follows its regulation