USER MANUAL – Release 1.2 of 01/01/2010 Page 160 of 191
57.9 LOW EVAPORATION PRESSURE IF THE LOW PRESSURE TRANSDUCERS
ARE USED
Warning, if low pressure transducers are configured, the low pressure alarm regulation only takes place on
the same.
b1lP (circuit n° 1 analogue input low pressure)
b2lP (circuit n° 2 analogue input low pressure)
b3lP (circuit n° 3 analogue input low pressure)
b4lP (circuit n° 4 analogue input low pressure)
The alarm is activated when at least one pressure probe configured as the
evaporation control measures a temperature < AL03 set in the following
conditions:
• working in cooling or heating mode
• stand-by or OFF-remote if AL08 = 1
! In defrost if AL06=1
The alarm is not signalled:
• in defrost for time AL07 in correspondence with valve inversion
• on compressor switch-on for the time AL01
If the evaporation control probe measures a temperature > of the AL03 set +
differential AL04
Automatic – it becomes manual after AL05 interventions/hour (reset procedure
in functions menu)
it follows its regulation
it follows its regulation