USER MANUAL – Release 1.2 of 01/01/2010 Page 187 of 191
57.40 REMOTE TERMINAL ALARM
Incorrect connection between remote terminal and controller or two remote
terminals configured as present and both with the same HW address
Correct connection - two different HW addresses
Alarm relay + buzzer activated
They follow their regulation
57.41 NOTE: ALARM RELAY AND BUZZER
The alarm relay working is enabled with at least one relay configured as alarm
Alarm relay/buzzer outlet
1. In the presence of active alarms
2. In the presence of alarms not resetted
1. In absence of alarms
2. In stand-by or ON - remote OFF if AL65=1
3. (buzzer) pressing one of the keys even in the presence of non-resettable alarms
58. NO VOLTAGE
On restore:
1. the device goes to the status preceding the power cut.
2. If a defrost cycle is progress the cycle is resetted.
3. All timings in progress are annulled and re-initialised.
4. If a manual reset alarm is present, the alarm status is maintained until the key is used to restore
conditions.
59. AUTOMATIC TO MANUAL RESRT ALARMS DIAGNOSTICS
N° OCCURRENCES PER HOUR
Every hour is divided into 60 intervals, 1 minute each.
On device start every observation interval is marked as "not active".
At the beginning of every observation interval it is marked "not active" and so on until it is concluded. It is
marked "active" if at least one alarm has occurred.
At the end of every observation interval, move to the next remembering that it is continuous observation and
when the first 60 intervals have finished the 61
st
overwrites the first, the 62
nd
overwrites the 2
nd
and so on.
The last hour of work is always monitored in this way and all "active" intervals can be counted. When the n°
of active intervals exceeds the threshold set, the alarm becomes manual. By setting the threshold at 0 the
alarm will be manual already at its first intervention, while by setting the threshold at 60 the alarm will always
be automatic reset as 61 observation intervals do not exist.