USER MANUALRelease 1.2 of 01/01/2010 Page 186 of 191
Version: 02/03/2010
ACF14
The temperature control has been configured on two circuits (ST12 = 1) but:
the second circuit is not configured or circuits 3 and/or 4 are also
configured
free cooling and/or recovery and/or domestic hot water are enabled
ACF15
Free cooling enabled but:
the on/off valve and the damper proportional output are not defined
the evaporator water inlet or free cooling water inlet or external air
temperature probes are not defined
ACF16
Production of domestic hot water enabled but:
the unit is configured as air/air (CF01 = 0)
the domestic hot water pump outlet relay and OUT1 are not defined
the domestic hot water regulation probe 1 is not defined
ACF17
one or more pressure probes defined on a XEV20D module not configured
on parameters Et09 Et16
Cause of activation
Incorrect programming
Reset
Correct programming
Reset
Automatic
Icon
flashing
Action
Alarm relay + buzzer activated
Regulators
Alarm
Relay + buzzer activated
Other loads
Off