USER MANUAL – Release 1.2 of 01/01/2010 Page 25 of 191
Defines the circuit 2 temperature control probe in cooling mode
0= Evaporator inlet NTC temperature probe
1= Evaporator n° 1 outlet NTC temperature probe
2= Evaporator n° 2 outlet NTC temperature probe
3= Evaporator n° 3 outlet NTC temperature probe
4= Evaporator n° 4 outlet NTC temperature probe
5= Evaporator common outlet NTC temperature probe
6= n° 1 remote terminal temperature probe (Not Available)
7= n° 2 remote terminal temperature probe (Not Available)
Defines the circuit n°2 temperature control probe in heating mode
0= Evaporator inlet NTC temperature probe
1= Evaporator n° 1 outlet NTC temperature probe
2= Evaporator n° 2 outlet NTC temperature probe
3= Evaporator n° 3 outlet NTC temperature probe
4= Evaporator n° 4 outlet NTC temperature probe
5= Evaporator common outlet NTC temperature probe
6= n° 1 remote terminal temperature probe
7= n° 2 remote terminal temperature probe
8= condenser water common inlet NTC temperature probe
9= circuit n° 1 condenser water inlet NTC temperature probe
10= circuit n° 2 condenser water inlet NTC temperature probe
11= circuit n° 3 condenser water inlet NTC temperature probe
12= circuit n° 4 condenser water inlet NTC temperature probe
13= circuit n° 1 condenser water outlet NTC temperature probe
14= circuit n° 2 condenser water outlet NTC temperature probe
15= circuit n° 3 condenser water outlet NTC temperature probe
16= circuit n° 4 condenser water outlet NTC temperature probe
17=condenser water common outlet NTC temperature probe
Circuit N° 1 PID regulation
Circuit n° 1 proportional band
Circuit n° 1 integral time
Circuit n° 1 derivative time
Circuit n° 1 derivative part multiplier
Circuit N° 2 PID regulation
Circuit n° 2 proportional band
Circuit n° 2 integral time
Circuit n° 2 derivative time
Circuit n° 2 derivative part multiplier
Activation offset for compressors.
When the controlled temperature (coming from neutral zone) enters the
compressors activation zone the compressors/capacity steps are enabled
only if the variable exceeds (in cooling) or drops below (in heating) the
relevant threshold for at least ST31.
Compressor ON Delay time. The controlled variable must be over (in cooling)
or under (in heating) the above mentioned activation level for at least the
ST32 time before the compressor/capacity step is switched ON.
Disabling offset for compressors.
When the controlled temperature (coming from neutral zone) enters the
compressors disabling zone the compressors/capacity steps are disabled only
if the variable drops below (in cooling) or exceeds(in heating) the relevant
threshold of at least ST33.
Compressor OFF Delay time.
The controlled variable must be under (in cooling) or over (in heating) the
above mentioned activation level for at least the ST34 time before the
compressor/capacity step is switched OFF.
Analogue input to be shown on first row of the 1
st
Visograph keyboard
0 = no display (the line remains empty)
Analogue input to be shown on second row of the 1
st
Visograph keyboard
Analogue input to be shown on third row of the 1
st
Visograph keyboard
Analogue input to be shown on fourth row of the 1
st
Visograph keyboard
Analogue input to be shown on first row of the 2
nd
Visograph keyboard
Analogue input to be shown on second row of the 2
nd
Visograph keyboard
Analogue input to be shown on third row of the 2
nd
Visograph keyboard
Analogue input to be shown on fourth row of the 2
nd
Visograph keyboard