Compliance
31
XR2400F Installation Guide
2500 N. Partnership Boulevard Springfield, MO 65803 www.dmpnet.com Digital Monitoring Products
UL 985 NFPA 72 (Chapter 2) SPECIFICATIONS
Household Fire Warning System Units
31.1 Bell output definition
The Bell Output of the Model XR2400F must be programmed to operate steady on burglary alarms and pulsed
or temporal on fire alarms. See section 8 of the Programming Guide (LT-0196).
UL 864 NFPA 72 (Chapter 9) SPECIFICATIONS
Control Units for Fire-Protective Signaling Systems
32.1 Zone restoral reports
The Restoral Reports option must be selected as YES or DISARM. See section 6.3 in the Programming Guide
(LT-0196).
32.2 Power fail delay
The Power Fail Delay option must be selected as 6 hours. See section 7.6 of the Programming Guide (LT-0196).
32.3 Sprinkler supervisory
Any zone used for sprinkler supervisory must be programmed with "SPRINKLR XXX" as the zone name. The
last three characters in the zone name may be assigned a number to identify the zone. The Model 893 or 893A
Dual Phone Line Module must be used on all sprinkler supervisory systems.
32.4 DACT systems
Two phone lines must be used. The two phone lines cannot be ground start or party lines. The 893 or 893A Dual
Phone Line Module is used to provide connection of two phone lines to the system. The 2ND Phone Line
communication option must be selected as YES. See section 3.3 of the Programming Guide (LT-0196).
Two different phone numbers must be programmed for digital communication. See sections 3.17 and 3.18 of
the Programming Guide (LT-0196). The Test Time option must be programmed so that the XR2400F sends a
report every 24 hours. See sections 3.8 to 3.10 of the Programming Guide (LT-0196).
Additionally, you can use the 462N Network Interface Card and the HST (Host) Communication type for
supplementary communication over digital data networks.
32.5 Type 2 and Type 3 Central Station Service
Type 2 and Type 3 Central Station Service can be provided by using MPX communication to the DMP SCS-1
Receiver system. See section 3.2 of the Programming Guide (LT-0196).
32.6 Type 1 Central Station Service
Type 1 Central Station Service can be provided by using MPX as the main communication and digital dialer as
backup. The 893 Dual Phone Line Module is used to provide connection of the MPX and dialer lines. See
section 3.2 of the Programming Guide (LT-0196). If Type 1 Central Station service is provided, the Test Time
option must be programmed to send a report every 24 hours. See sections 3.8 to 3.10 of the Programming
Guide (LT-0196).
With both Type 1 and Type 2 Central Station service, the total number of panels assigned to a standard MPX
receiving line of the SCS-1 Receiver System must not exceed 90. This may be increased to 180 by setting the
SNRM option to NO in the SCS-1 Receiver system. This is to allow any signal from a XR2400F to be
transmitted to the receiver within 90 seconds.
32.7 Local Protective Signaling Systems
The DMP Model 865, 866, or 867 Notification Circuit Module must be used on the bell circuit for detection of
shorts and grounds. See sections 25.1 to 25.3 for wiring diagrams. Model 770 series keypads that are used to
display troubles for local fire alarm systems must be installed within a DMP Model 777 Keypad Protector. Model
790 series keypads that are used to display troubles for local fire alarm systems must be installed within a DMP
Model 777 with 777S 1.0" spacer. Any burglary or other off premises communication must be done with the
Model 893 or 893A Dual Phone Line Module.