Compliance
30
XR2400F Installation Guide
Digital Monitoring Products www.dmpnet.com 2500 N. Partnership Boulevard Springfield, MO 65803
UNIVERSAL UL and NFPA FIRE ALARM SPECIFICATIONS
30.1 Introduction
The programming and installation specifications contained in this section must be completed when installing the
Model XR2400F in accordance with any of the UL or NFPA fire standards. Additional specifications may be
required by a particular standard.
30.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
30.3 Transformer
A wire-in transformer should be used. Use the 16 VAC 40VA DMP Model 320. The transformer must be
mounted within 20 feet of the panel connected by conduit.
30.4 End Of Line resistor
The DMP Model 310 1k Ohm EOL resistor should be used on all 1k Ohm EOL fire zones.
30.5 System trouble display
The Status List Display must include at least one keypad that displays system monitor troubles. See section
10.3 of the Programming Guide (LT-0196).
30.6 Fire display
The Status List Display must include at least one keypad that displays troubles and alarms on fire type zones.
See section 10.4 of the Programming Guide (LT-0196).
30.7 Police station phone number
The digital dialer telephone number programmed for communication must not be a police station phone number,
unless that phone number is specifically provided for that purpose.
30.8 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end
user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance
program and acquainting the user with the correct procedure for use and testing of the system is also the
responsibility of the installing alarm company.
30.9 Audible alarm
Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones should
not be programmed as “N”. See section 8.4A in the Programming Guide (LT-0196).
30.10Fire zone programming
If a retard delay is used on a waterflow zone, it cannot exceed 90 seconds and any retard delay in the waterflow
initiating devices must be subtracted from the 90 seconds allowed. See sections 13.4 and 13.17 in the
Programming Guide (LT-0196). The retard delay should not be used on a zone with smoke detectors.
30.11Style D zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Style D zones to the
Model XR2400F. See section Dual Style D Zone Module Installation in System Wiring Diagrams and the 869
Installation Guide (LT-0186) for wiring information.
30.12Video Option
The Video option must be selected as NO when any fire protection is connected to the XR2400F. See section
7.9 in the Programming Guide (LT-0196).
30.13UL Listed Receivers
UL has verified operation with the DMP SCS-1 (SDLC), Sur-Gard SG-HLR2-DG (CID, M2E), FBII CP220PB
(CID), Osborne-Hoffman Quick-Alert (CID, M2E), and Radionics D6500 (M2E) receivers.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DMP Electronics XR2400F and is the answer not in the manual?

DMP Electronics XR2400F Specifications

General IconGeneral
BrandDMP Electronics
ModelXR2400F
CategoryControl Panel
LanguageEnglish

Related product manuals