EasyManua.ls Logo

Ducati R5 - Overcurrent Alarm Delay

Ducati R5
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MU-MID-R5-D-ENG.doc
Page28 of 70
Example 1: if CT primary winding = 5, the possible settable values are [6.00; 5.95; 5.90; 5.85; 5.80; 5.75; 5.70;
5.65; 5.60; 5.55; 5.50; 5.45; 5.40; 5.35; 5.30; 5.25; 5.20; 5.15; 5.10; 5.05; 5.00; 4.95; 4.90; 4.85; 4.80; 4.75; 4.70; 4.65;
4.60; 4.55; 4.50; OFF).
Example 2: if CT primary winding = 5.00k and you wish to set the threshold at 105% (5.25kA), scroll the
suggested values and set:
Example 3: to disable the alarm set:
After parameter is confirmed, the controller will move to the next parameter setting screen (Overcurrent alarm
delay).
7.5.4 Overcurrent alarm delay
The default value is "10". The permitted range for the parameter is [1÷255] seconds.
NOTE: the alarm will be activated and deactivated if the reference measurement steadily stays above or under the
threshold for the time set.
If a permitted value is entered, the controller will move to the next parameter setting screen (Low voltage alarm
threshold).
7.5.5 Low voltage alarm threshold
The default value is "OFF". The possible permitted values for the parameter will range from 90% to 110% of the
value set for parameter VT primary winding with a 1% resolution. To disable the alarm select the "OFF" value.
Example 1: if VT primary winding = 400, the possible settable values are [440; 436; 432; 428; 424; 420; 416; 412;
408; 404; 400; 396; 392; 388; 384; 380; 376; 372; 368; 364; 360; OFF].
Example 2: if VT primary winding = 5.00kand you wish to set the threshold at 95% (4.75kV), scroll the suggested
values and set:

Table of Contents

Related product manuals