After parameter is confirmed, the controller will move to the next parameter setting screen (Low voltage alarm
delay).
7.5.6 Low voltage alarm delay
The default value is "10". The permitted range for the parameter is [1÷255] seconds.
NOTE: the alarm will be activated and deactivated if the reference measurement steadily stays above or under the
threshold for the time set.
If a permitted value is entered, the controller will move to the next parameter setting screen (Low current alarm
threshold).
7.5.7 Low current alarm threshold
The default value is "0.03". The possible permitted values for the parameter will range from 0.7% to 10% of the value
set for parameter CT primary winding with a 0.5% resolution.
Example 1: if CT primary winding = 5, the possible settable values are [0.03; 0.05; 0.08; 0.10; 0.13; 0.15; 0.18;
0.20; 0.23; 0.25; 0.28; 0.30; 0.33; 0.35; 0.38; 0.40; 0.43; 0.45; 0.48; 0.50].
Example 2: if CT primary winding = 5.00k and you wish to set the threshold at 5% (250A), scroll the suggested
values and set:
After parameter is confirmed, the controller will move to the next parameter setting screen (Low current alarm
delay).
7.5.8 Low current alarm delay
The default value is "10". The permitted range for the parameter is [1÷255] seconds.
NOTE: the alarm will be activated and deactivated if the reference measurement steadily stays above or under the
threshold for the time set.
If a permitted value is entered, the controller will move to the next parameter setting screen (THDV alarm
threshold).