7.5.9 THDV alarm threshold
The default value is "999". The permitted range for the parameter is [1%÷100%]. To disable the alarm enter value
"999"
Example: to set the threshold at 10%, enter:
If a permitted value is entered, the controller will move to the next parameter setting screen (THDV alarm delay).
7.5.10 THDV alarm delay
The default value is "10". The permitted range for the parameter is [1÷255] seconds.
NOTE: the alarm will be activated and deactivated if the reference measurement steadily stays above or under the
threshold for the time set.
If a permitted value is entered, the controller will move to the next parameter setting screen (THDI alarm threshold).
7.5.11 THDI alarm threshold
The default value is "999". The permitted range for the parameter is [1%÷100%]. To disable the alarm enter value
"999"
Example 1: to set the threshold at 10%, enter:
If a permitted value is entered, the controller will move to the next parameter setting screen (THDI alarm delay).