that will be alternately shown with the previously set value (2kVAr in the example shown). Edit, if necessary, the
suggested value. If the controller is installed on a Ducati energia power factor correction equipment, the value to be
entered is the one specified on equipment plate (for the entering mode of the numerical value, refer to Chap. 7.8 -
Numerical value entering modes).
8.6.2 Bank n contactor switching manoeuvres number reset (n=1,2,3,4,5)
If you want to reset bank n, scroll the suggested values until reaching parameter “OPn” flashing
(with n=1,2,3,4,5). The example screen relates to bank 1.
The reset of the bank n contactor switching manoeuvres number will reset only the OP
parameter of the contactor associated to bank n.
Confirm the reset of the parameter by pressing key for at least 2sec. The controller will automatically move to
the first Setup Menu page.
8.6.3 Alarm reset
Scroll the suggested values until reaching parameter “ALA” flashing.
The alarm reset will result in the reset of the occurrence counters of all the alarms displayed in
the Statistics Menu (Chap. 8.4).
Confirm the reset of the parameter by pressing key for at least 2sec. The controller will
automatically move to the first Setup Menu page.
8.6.4 Average value reset
Scroll the suggested values until reaching parameter “AVG” flashing.
The reset of average values will result in the reset of the average values of voltage, current,
reactive power, active power, apparent power, cosphi, PF and temperature measurements as
well as of the daily, weekly and monthly cosphi average value.
NOTE: average values are only available via the communication interfaces RS485 and Radio 868MHz for the
provided models.
Confirm the reset of the parameter by pressing key for at least 2sec. The controller will automatically move to
the first Setup Menu page.
8.6.5 Minimum and maximum value reset
Scroll the suggested values until reaching parameter “PEA” flashing.
The reset of maximum and minimum values will result in the reset of the maximum and
minimum values of voltage, current, reactive power, active power, apparent power, cosphi, PF
and temperature measurements.
NOTE: minimum and maximum values are only available via the communication interfaces RS485 and Radio
868MHz for the provided models.
Confirm the reset of the parameter by pressing key for at least 2sec. The controller will automatically move to
the first Setup Menu page.