Eldan Recycling A/S Page 16
4.1.2 Procedure for adjustment of the inlet conveyor.
Set P, then I, then D and at last S.
Standard setting:
SV = Setting of Max. Load value of MPR.
P = 300 (1 to 9999)
(30%) (0.1 to 999.9%)
I = 5 (1 til 8191)
( 0.5sek) (0.1 til 99.9 sek.)
D = 1 (1 to 8191)
( 0.1 Sek.) (0.1 to 99.9 sek.)
S = 50 (1 to 9999)
( 0.5 Sek.) (0.01 to 99.99 sek.)
P = proportional to inlet conveyor (P)
Regulates the speed from the set value (Max. Load value of TR).
I = Integral constant (Tik)
Equalize P to an even flow into TR.
=
=