Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
148 Affinity User Guide
www.controltechniques.com Issue Number: 5
Parameter
Range(
Ú) Default(Ö)
Type
OL RFC OL RFC
1.01
Frequency / speed
reference selected
±SPEED_FREQ_MAX Hz/rpm
RO Bi NC PT
1.02 Pre-skip filter reference RO Bi NC PT
1.03 Pre-ramp reference RO Bi NC PT
1.04 Reference offset ±3,000.0Hz ±40,000.0 rpm 0.0 RW Bi US
1.05 Jog reference 0 to 400.0 Hz 0 to 4,000.0 rpm 0.0 RW Uni US
1.06 Maximum reference clamp {0.02} 0 to 3,000.0 Hz SPEED_LIMIT_MAX rpm
EUR> 50.0
USA> 60.0
EUR> 1,500.0
USA> 1,800.0
RW Uni US
1.07 Minimum reference clamp {0.01} ±3,000.0 Hz ±SPEED_LIMIT_MAX rpm 0.0 RW Bi PT US
1.08
Negative minimum
reference clamp enable
OFF (0) or On (1)
OFF (0)
RW Bit US
1.09 Reference offset select RW Bit US
1.10 Bipolar reference enable RW Bit US
1.11
Reference enabled
indicator
RO Bit NC PT
1.12 Reverse selected indicator RO Bit NC PT
1.13 Jog selected indicator RO Bit NC PT
1.14 Reference selector {0.05} A1.A2 (0), A1.Pr (1), A2.Pr (2), Pr (3), PAd (4), Prc (5) A1.A2 (0) RW Txt US
1.15 Preset reference selector 0 to 9 0 RW Uni US
1.16
Preset reference selector
timer
0 to 400.0s 10.0 RW Uni US
1.17
Keypad control mode
reference
±SPEED_FREQ_MAX Hz/rpm 0.0 RO Bi NC PT PS
1.18 Precision reference coarse ±SPEED_FREQ_MAX Hz/rpm 0.0 RW Bi US
1.19 Precision reference fine 0.000 to 0.099 Hz 0.000 to 0.099 rpm 0.000 RW Uni US
1.20
Precision reference update
disable
OFF (0) or On (1) OFF (0) RW Bit NC
1.21 Preset reference 1
±SPEED_FREQ_MAX Hz/rpm 0.0
RW Bi US
1.22 Preset reference 2 RW Bi US
1.23 Preset reference 3 RW Bi US
1.24 Preset reference 4 RW Bi US
1.25 Preset reference 5 RW Bi US
1.26 Preset reference 6 RW Bi US
1.27 Preset reference 7 RW Bi US
1.28 Preset reference 8 RW Bi US
1.29 Skip reference 1 0.0 to 3,000.0 Hz 0 to 40,000 rpm 0.0 0 RW Uni US
1.30 Skip reference band 1 0.0 to 25.0 Hz 0 to 250 rpm 0.5 5 RW Uni US
1.31 Skip reference 2 0.0 to 3,000.0 Hz 0 to 40,000 rpm 0.0 0 RW Uni US
1.32 Skip reference band 2 0.0 to 25.0 Hz 0 to 250 rpm 0.5 5 RW Uni US
1.33 Skip reference 3 0.0 to 3,000.0 Hz 0 to 40,000 rpm 0.0 0 RW Uni US
1.34 Skip reference band 3 0.0 to 25.0Hz 0 to 250 rpm 0.5 5 RW Uni US
1.35 Reference in rejection zone OFF (0) or On (1)
RO Bit NC PT
1.36 Analog reference 1
±SPEED_FREQ_MAX Hz/rpm
RO Bi NC
1.37 Analog reference 2
RO Bi NC
1.38 Percentage trim ±100.00% 0.00 RW Bi NC
1.41 Analog reference 2 select
OFF (0) or On (1) OFF (0)
RW Bit NC
1.42 Preset reference select RW Bit NC
1.43 Keypad reference select RW Bit NC
1.44 Precision reference select RW Bit NC
1.45 Preset reference 1 select RW Bit NC
1.46 Preset reference 2 select RW Bit NC
1.47 Preset reference 3 select RW Bit NC
1.48 Reference timer reset flag RW Bit NC
1.49
Reference selected
indicator
1 to 5
RO Uni NC PT
1.50
Preset reference selected
indicator
1 to 8
RO Uni NC PT
1.51
Power-up keyboard control
mode reference
rESEt (0), LASt (1), PrS1 (2) rESEt (0) RW Txt US
1.52
Enable hand/off/auto
keypad operation mode
0 to 3 1 RW Uni US
1.53 Fire mode reference ±SPEED_FREQ_MAX Hz/rpm 0.0 RW Bi US
1.54 Fire mode activate OFF (0) or On (1) OFF (0) RO Bit NC
RW Read / Write RO Read only Uni Unipolar Bi Bi-polar Bit Bit parameter Txt Text string
FI Filtered DE Destination NC Not copied RA Rating dependent PT Protected US User save PS Power down save