Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
204 Affinity User Guide
www.controltechniques.com Issue Number: 5
SM-I/O PELV parameters
*See trip SLX.Er,
Automation (I/O Expansion) module category
on page 257.
Parameter
Range(
Ú) Default(Ö)
Type
x.01 Solutions Module ID 0 to 599 204 RO Uni PT US
x.02 Solutions Module software version 0.00 to 99.99
RO Uni NC PT
x.03 T5 digital I/O 3 state
OFF (0) or On (1)
RO Bit NC PT
x.04 T6 digital I/O 4 state RO Bit NC PT
x.05 T7 digital input 5 state RO Bit NC PT
x.07 Relay 1 state RO Bit NC PT
x.08 Relay 2 state RO Bit NC PT
x.09 T3 digital I/O 1 state RO Bit NC PT
x.10 T4 digital I/O 2 state RO Bit NC PT
x.11 T3 digital I/O 1 invert
OFF (0)
RW Bit US
x.12 T4 digital I/O 2 invert RW Bit US
x.13 T5 digital I/O 3 invert RW Bit US
x.14 T6 digital I/O 4 invert RW Bit US
x.15 T7 digital input 5 invert RW Bit US
x.16
Disable PELV User power
supply absent trip
RW Bit US
x.17 Relay 1 invert RW Bit US
x.18 Relay 2 invert RW Bit US
x.19 Freeze flag RW Bit US
x.20 Digital I/O read word 0 to 255
RO Uni NC PT
x.21 T3 digital I/O 1 source/destination
Pr 0.00 to Pr 50.99 Pr 0.00
RW Uni DE PT US
x.22 T4 digital I/O 2 source/destination RW Uni DE PT US
x.23 T5 digital I/O 3 source/destination RW Uni DE PT US
x.24 T6 digital I/O 4 source/destination RW Uni DE PT US
x.25 T7 digital input 5 destination RW Uni DE PT US
x.27 Relay 1 source RW Uni PT US
x.28 Relay 2 source RW Uni PT US
x.29 T6 digital I/O 4 output select
OFF (0) or On (1)
On (1) RW Bit US
x.31 T3 digital I/O 1 output select
OFF (0)
RW Bit US
x.32 T4 digital I/O 2 output select RW Bit US
x.33 T5 digital I/O 3 output select RW Bit US
x.38 Analog input 1 mode
0-20 (0), 20-0 (1), 4-20.tr (2), 20-4.tr (3),
4-20 (4), 20-4 (5)
0-20 (0) RW Txt US
x.39 Analog output mode 0-20 (0), 20-0 (1), 4-20 (2), 20-4 (3) 0-20 (0) RW Txt US
x.40 Analog input 1 level 0.0 to 100.0%
RO Bi NC PT
x.41 Analog input 1 scaling 0.000 to 4.000 1.000 RW Uni US
x.42 Analog input 1 invert OFF (0) or On (1) OFF (0) RW Bit US
x.43 Analog input 1 destination Pr 0.00 to Pr 50.99 Pr 0.00 RW Uni DE PT US
x.45 Analog output 2 scaling 0.000 to 4.000 1.000 RW Uni US
x.47 Analog output 2 source
Pr 0.00 to Pr 50.99 Pr 0.00
RW Uni PT US
x.48 Analog output 1 source RW Uni PT US
x.49 Analog output 1 scaling 0.000 to 4.000 1.000 RW Uni US
x.50 Solutions Module error status* 0 to 255
RO Uni NC PT
x.51
Solutions Module software sub-version
0 to 99 RO Uni NC PT
RW Read / Write RO Read only Uni Unipolar Bi Bi-polar Bit Bit parameter Txt Text string
FI Filtered DE Destination NC Not copied RA Rating dependent PT Protected US User save PS Power down save