Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting
Started
Basic
parameters
Running
the motor
Optimization
SMARTCARD
operation
PC tools
Advanced
parameters
Technical
Data
Diagnostics
UL Listing
Information
Affinity User Guide 229
Issue Number: 5 www.controltechniques.com
Table 12-2 Maximum permissible continuous output current @ 40°C (104°F) ambient for size 1 to 6 standard, size 1 to 3 E12/E54 and size
1 to 3 E12/E66 drives
For the definition of ambient temperature, see section 3.7 Enclosure design and drive ambient temperature on page 49.
Model
Nominal rating Maximum permissible continuous output current (A) for the following switching frequencies
3kHz 4kHz 6kHz 8kHz 12kHz 16kHzkW hp
BA1201 1.1 1.5 5.2
BA1202 1.5 2.0 6.8
BA1203 2.2 3.0 9.6
BA1204 3.0 3.0 11.0
BA2201 4.0 5.0 15.5
BA2202 5.5 7.5 22.0
BA2203 7.5 10 28.0 27.9 24.8 21.8
BA3201 11 15 42.0
BA3202 15 20 54.0 48.5
BA4201 18.5 25 68.0
BA4202 22 30 80.0
BA4203 30 40 104
BA5201 37 50 130
BA5202 45 60 154
BA1401 1.1 1.5 2.8
BA1402 1.5 2.0 3.8
BA1403 2.2 3.0 5.0
BA1404 3.0 5.0 6.9 5.9
BA1405 4.0 5.0 8.8 7.4 5.7
BA1406 5.5 7.5 11.0 10.0 7.4 5.7
BA2401 7.5 10 15.3 12.7 10.1
BA2402 11 15 21.0 19.5 16.7 12.7 10.0
BA2403 15 20 29.0 27.2 23.2 20.0 15.0 11.8
BA3401 18.5 25 35.0 30.3 22.4 17.4
BA3402 22 30 43.0
39.5
32.8 24.0 18.5
BA3403 30 40 56.0 48.7 39.5 32.8 24.0
BA4401 37 50 68.0 62.0
BA4402 45 60 83.0 74.0 63.0
BA4403 55 75 104 95.1 78.8
BA5401 75 100 138 118 97.1
BA5402 90 125 168 158 129 107
BA6401 110 150 205 164.1
BA6402 132 200 236 210.4 157.7
BA3501 3.0 3.0 5.4
BA3502 4.0 5.0 6.1
BA3503 5.5 7.5 8.4
BA3504 7.5 10 11.0
BA3505 11 15 16.0
BA3506 15 20 22.0 21.6 18.2
BA3507 18.5 25 27.0 26.0 21.6 18.1
BA4601 18.5 25 22.0
BA4602 22 30 27.0
BA4603 30 40 36.0 33.9
BA4604 37 50 43.0 41.3 33.7
BA4605 45 60 52.0 51.9 41.2 33.7
BA4606 55 75 62.0 61.3 48.4 39.6
BA5601 75 100 84 69 54
BA5602 90 125 99 91 69 54
BA6601 110 150 125 100 74
BA6602 132 175 144 100 74