Page #250 background image
246 EZMotion User/Programming Guide
www.controltechniques.com Revision: A8
6. Restore power to the Unidrive SP
After performing the clear memory sequence, the SM-EZMotion module will cause a SLX.Er trip (where X indicates the slot number
that the SM-EZMotion module is fitted in). The Error Code for the SM-EZMotion module will be “107 – No Program Error” indicating
that the module has no configuration stored in it. Download a new configuration using PowerTools Pro to clear the trip.