7.3.3 RFC-A mode (Sensorless control)
Induction motor with sensorless control
Action Detail
Before power-up
Ensure:
The drive enable signal is not given (terminals 11 and 13)
Run signal is not given
Motor and feedback device are connected
Power-up the
drive
Verify that RFC-A mode is displayed as the drive powers up. If the mode is incorrect see section 5.6 Changing
the operating mode on page 93.
Ensure:
Drive displays ‘Inhibit’
If the drive trips, see Chapter 13 Diagnostics on page 247.
Select RFC-A
(Sensorless
control) mode
and disable
encoder wire-
break trip
•Set Pr 03.024 = 1 or 3 to select RFC-A Sensorless mode
•Set Pr 03.040 = 0000 to disable the wire break
Enter motor
nameplate
details
Enter:
Motor rated frequency in Pr 00.047 (Hz)
Motor rated current in Pr 00.046 (A)
Motor rated speed in Pr 00.045 (rpm)
Motor rated voltage in Pr 00.044 (V) - check if or connection
Set maximum
speed
Enter:
Maximum speed in Pr 00.002 (rpm)
Set acceleration /
deceleration
rates
Enter:
Acceleration rate in Pr 00.003 (s/1000rpm)
Deceleration rate in Pr 00.004 (s/1000rpm) (If braking resistor installed, set Pr 00.015 = Fast. Also ensure
Pr 10.030, Pr 10.031 and Pr 10.061 are set correctly, otherwise premature ‘Brake R Too Hot’ trips may be
seen).
Select or
deselect catch a
spinning motor
mode
If catch a spinning motor mode is not required then set Pr 06.009 to 0.
If catch a spinning motor mode is required then leave Pr 06.009 at the default of 1, but depending on the size
of the motor the value in Pr 05.040 may need to be adjusted.
Pr 05.040 defines a scaling function used by the algorithm that detects the speed of the motor. The default
value of Pr 05.040 is 1 which is suitable for small motors (<4 kW). For larger motors the value in Pr 05.040 will
need to be increased. Approximate values of Pr 05.040 for different motor sizes are as follows, 2 for 11 kW, 3
for 55 kW and 5 for 150 kW. If the value of Pr 05.040 is too large the motor may accelerate from standstill
when the drive is enabled. If the value of this parameter is too small the drive will detect the motor speed as
zero even if the motor is spinning.
Autotune
The drive is able to perform either a stationary or a rotating autotune. The motor must be at a standstill before
an autotune is enabled. A stationary autotune will give moderate performance whereas a rotating autotune will
give improved performance as it measures the actual values of the motor parameters required by the drive.
It is highly recommended that a rotating autotune is performed (Pr 00.040 set to 2).
A stationary autotune can be used when the motor is loaded and it is not possible to uncouple the load
from the motor shaft. The stationary autotune measures the stator resistance and transient inductance of
the motor. These are used to calculate the current loop gains, and at the end of the test the values in
Pr 00.038 and Pr 00.039 are updated. A stationary autotune does not measure the power factor of the
motor so the value on the motor nameplate must be entered into Pr 00.043.
A rotating autotune should only be used if the motor is uncoupled. A rotating autotune first performs a
stationary autotune before rotating the motor at 2/3 base speed in the direction selected. The rotating
autotune measures the stator inductance of the motor and calculates the power factor.
To perform an autotune:
•Set Pr 00.040 = 1 for a stationary autotune or set Pr 00.040 = 2 for a rotating autotune
Close the drive enable signal (terminals 11 and 13). The drive will display ’Ready’ or ‘Inhibit’.
Close the run signal (terminal 7 or 8). The
upper row of the display will flash ’Auto Tune’ while the drive is
performing the autotune.
Wait for the drive to display ’Ready’ or ‘Inhibit’ and for the motor to come to a standstill.
If the drive trips, see Chapter 13 Diagnostics on page 247.
Remove the drive enable and run signal from the drive.
Save parameters
Select 'Save Parameters' in Pr
MM.000
(alternatively enter a value of 1000 in Pr
MM.000
) and press red
reset button or toggle the reset digital input.
Run Drive is now ready to run
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55 I.cl F C 40 s S1
°
VHzmin
-1
kW cos
φ
A
230
400
50 1445 2.20 0.80 8.50
4.90
CN = 14.5Nm
240
415
50 1445 2.20 0.76 8.50
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
I.E.C 34 1(87)
0.02
t
1000rpm
0.03
t
0.04
NOTE
A rotating autotune will cause the motor to accelerate up to
2
/
3
base speed in the direction selected
regardless of the reference provided. Once complete the motor will coast to a stop. The enable
signal must be removed before the drive can be made to run at the required reference.
The drive can be stopped at any time by removing the run signal or removing the drive enable.
WARNING
cos
σ
L
S
T
Nm
N rpm
saturation
break-
points
R
S
L
S