Unidrive M702 User Guide             61
Issue Number: 3            
 
Ensure cables used suit local wiring regulations.
Table 4-9 Cable ratings (200 V)
The nominal cable sizes below are only a guide. The mounting and grouping of cables affects their current-carrying capacity, in some cases 
smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop. Refer to 
local wiring regulations for the correct size of cables.
Model
Cable size   (IEC)
mm
2
Cable size   (UL)
AWG
Input Output Input Output
Nominal Maximum Nominal  Maximum Nominal  Maximum Nominal Maximum
03200050
1.5
4
1.5
4
14
10
14
10
03200066
03200080
44
12 12
03200106
04200137
6
8
6
8
10
8
10
8
04200185
8
888
05200250
10
10 10 10 8 8 8 8
06200330
16
25
16
25
4
3
4
3
06200440
25
25 3 3
07200610
35
70
35
70
2
1/0
2
1/007200750 11
07200830
70
70 1/0 1/0
08201160
95
2 x 70
95
2 x 70
3/0
2 x 1
3/0
2 x 1
08201320 2 x 70 2 x 70 2 x 1 2 x 1