Unidrive M702 User Guide 183
Issue Number: 3
Parameter
Range(
) Default()
Type
OL RFC-A / S OL RFC-A RFC-S
08.001 Digital I/O 01 State Off (0) or On (1) RO Bit ND NC PT
08.002 Digital I/O 02 State Off (0) or On (1) RO Bit ND NC PT
08.004 Digital Input 04 State Off (0) or On (1) RO Bit ND NC PT
08.005 Digital Input 05 State Off (0) or On (1) RO Bit ND NC PT
08.007 Relay Output State Off (0) or On (1) RO Bit ND NC PT
08.008 24V Supply Output State Off (0) or On (1) RO Bit ND NC PT
08.009 STO Input 01 State Off (0) or On (1) RO Bit ND NC PT
08.010 External Trip Mode Disable (0), STO 1 (1), STO 2 (2), STO 1 OR STO 2 (3) Disable (0) RW Txt US
08.011 Digital I/O 01 Invert Not Invert (0) or Invert (1) Not Invert (0) RW Txt US
08.012 Digital I/O 02 Invert Not Invert (0) or Invert (1) Not Invert (0) RW Txt US
08.014 Digital Input 04 Invert Not Invert (0) or Invert (1) Not Invert (0) RW Txt US
08.015 Digital Input 05 Invert Not Invert (0) or Invert (1) Not Invert (0) RW Txt US
08.017 Relay Invert Not Invert (0) or Invert (1) Not Invert (0) RW Txt US
08.018 24V Supply Output Invert Not Invert (0) or Invert (1) Invert (1) RW Txt US
08.020 Digital I/O Read Word 0 to 511 RO Num ND NC PT
08.021 Digital I/O 01 Source/Destination 0.000 to 59.999 10.003 RW Num DE PT US
08.022 Digital I/O 02 Source/Destination 0.000 to 59.999 0.000 RW Num DE PT US
08.024 Digital Input 04 Destination 0.000 to 59.999 6.030 RW Num DE PT US
08.025 Digital Input 05 Destination 0.000 to 59.999 6.032 RW Num DE PT US
08.027 Relay Output Source 0.000 to 59.999 10.001 RW Num PT US
08.028 24V Supply Output Source 0.000 to 59.999 0.000 RW Num PT US
08.029 Input Logic Polarity Negative Logic (0) or Positive Logic (1) Positive Logic (1) RW Txt US
08.040 STO Input 02 State Off (0) or On (1) RO Bit ND NC PT
08.041 Keypad Run Button State Off (0) or On (1) RO Bit ND NC PT
08.042 Keypad Auxiliary Button State Off (0) or On (1) RO Bit ND NC PT
08.043 24V Supply Input State Off (0) or On (1) RO Bit ND NC PT
08.051 Keypad Run Button Invert/Toggle
Not Invert (0), Invert (1) or Toggle (2)
Not Invert (0) RW Txt US
08.052 Keypad Auxiliary Button Invert/Toggle Not Invert (0) RW Txt US
08.053 24V Supply Input Invert Not Invert (0) or Invert (1) Not Invert (0) RW Txt US
08.061 Keypad Run Button Destination 0.000 to 59.999 0.000 RW Num DE PT US
08.062 Keypad Auxiliary Button Destination 0.000 to 59.999 0.000 RW Num DE PT US
08.063 24V Supply Input Source 0.000 to 59.999 0.000 RW Num PT US
08.071 DI/O Output Enable Register 1 0000000000000000 to 1111111111111111 0000000000000000 RW Bin PT US
08.072 DI/O Input Register 1 0000000000000000 to 1111111111111111 0000000000000000 RO Bin PT
08.073 DI/O Output Register 1 0000000000000000 to 1111111111111111 0000000000000000 RW Bin PT
RW Read / Write RO Read only Num Number parameter Bit Bit parameter Txt Text string Bin Binary parameter FI Filtered
ND No default value NC Not copied PT Protected parameter RA Rating dependent US User save PS Power-down save DE Destination