Unidrive M702 User Guide 95
Issue Number: 3
Recommended cable
It is recommended that a minimum specification of CAT5e is used in new
installations. If the existing cabling is used this may limit the maximum
data rate depending on the cable ratings. In noisy environments the use
of STP cable will offer additional noise immunity.
Maximum network lengths
The main restriction imposed on the Ethernet cabling is the length of a
single segment of the cable, for Copper - UTP/STP CAT 5 cable type,
maximum trunk cable length should be limited to 100 m. If distances
greater than this are required it may be possible to extend the network
with additional switches.
Ethernet set-up parameters
The following section covers the minimum number of parameters
required to be set to establish an Ethernet communication.
Table 5-9 Key to parameter table coding
Changes to the Ethernet set-up parameters will not take effect until a
Reset (4.00.007) has been performed.
This parameter displays the Active IP Address. The Active IP Address
can also be viewed in Pr 00.037.
If DHCP Enable (4.02.005) is set to On (1), the IP address is acquired
from the DHCP server and written to IP Address (4.02.006).
When using manual / static IP address configuration, ensure Subnet
Mask (4.02.007) and Default Gateway (4.02.008) should also be set
manually.
This parameter controls and displays the IP address of the drive. If
DHCP Enable (4.02.005) is set to On (1) this parameter will become
read-only.
This parameter controls and displays the Subnet Mask (4.02.007) of the
drive.
This parameter controls and displays the Default Gateway (4.02.008) of
the drive.
PC Tools support
The discovery protocol feature, which is supported by the Unidrive M PC
tools, is able to discover the drives that are connected to a PC,
independent of above parameter settings.
RW Read / Write ND No default value
RO Read only NC Not copied
Num Number parameter PT Protected parameter
Bit Bit parameter RA Rating dependant
Txt Text string US User save
Bin Binary parameter PS Power-down save
FI Filtered DE Destination
IP IP Address Mac Mac Address
Date Date parameter Time Time parameter
4.00.007
{24.007}
Reset
RW Bit US
Off (0) or On (1)
Off (0)
4.00.010 Active IP Address
RO IP US
000.000.000.000 to
255.255.255.255
4.02.005 DHCP Enable
RW Bit US
Off (0) or On (1)
On (1)
4.02.006 IP Address
RW IP US
000.000.000.000 to
255.255.255.255
192.168.001.100
NOTE
4.02.007 Subnet Mask
RW IP US
000.000.000.000 to
255.255.255.255
255.255.255.000
4.02.008 Default Gateway
RW IP US
000.000.000.000 to
255.255.255.255
192.168.1.254