Description of parameters (FF configuration program) Cerabar S/Deltabar S
26 Endress+Hauser
MODE_BLK
Selection, Display
Index: 5
Data type: DS-69
Access: Auto, OOS
The MODE_BLK parameter is a structured parameter consisting of four elements.
The Resource Block supports the "Auto" (automatic mode) and OOS (out of service) modes.
TARGET
• Change the block mode.
ACTUAL
• Displays the current block mode.
PERMITTED
• Displays the modes supported by the block.
NORMAL
• Displays the block mode during standard operation.
NV_CYCLE_T/
NONVOLATILE CYCLE
TIME
Display
Index: 23
Data type: Unsigned32
Access: Read only
Displays the time interval in which the dynamic device parameters are stored in the non-
volatile memory. As Cerabar S and Deltabar S do not store dynamic device parameters in the
non-volatile memory, the parameter constantly displays the value 0
1
/
32
ms.
RESTART
Selection
Index: 16
Data type: Unsigned8
Access: Auto, OOS
Select reset mode.
Options:
• Run: standard operating mode
• Resource: this mode is not supported by Endress+Hauser.
• Defaults: device data and the function block link are reset to the factory setting. The
manufacturer-specific parameters of the Transducer Block are not reset to the factory
setting.
→ See also Operating Instructions BA301P (Deltabar S) or BA302P (Cerabar S),
Section 5.7 "Factory setting" (reset).
• Processor: warm start, of device, new processor start.
• Factory: the function block links, all FF and resettable manufacturer-specific parameters
are reset to the factory setting.
RS_STATE
Display
Index: 7
Data type: Unsigned8
Access: Read only
Displays the current status of the Resource Block.
Possibilities:
• Standby: the Resource Block is in the OOS mode (out of service). It is not possible to
execute the remaining blocks.
• Online linking: the configured links between the function blocks have not yet been
established.
• Online: standard block mode, the Resource Block works in the Auto mode. All the
configured links between the function blocks have been established. If a link is missing,
this parameter displays the "online linking" status.
SET_FSTATE/
SET FAULT STATE
Selection
Index: 29
Data type: Unsigned8
Access: Auto, OOS
Manually activate the fault state of the Discrete Output function block. → See also this table,
CLR_FSTATE parameter description.
Possibilities:
• Uninititalized
•Off
• Set (the fault state is activated.)
SHED_RCAS/
SHED REMOTE
CASCADE
Entry
Index: 26
Data type: Unsigned32
Access: Auto, OOS
Enter the monitoring time for checking the link between the fieldbus host system and the
PID function block in the RCAS block mode. Once this monitoring time elapses, the PID
function block changes from the RCAS block mode to the block mode selected by means of
the SHED_OPT parameter.
Factory setting:
640000
1
/
32
ms
SHED_ROUT/
SHED REMOTE OUT
Entry
Index: 27
Data type: Unsigned32
Access: Auto, OOS
Enter the monitoring time for checking the link between the fieldbus host system and the
PID function block in the ROUT block mode. Once this monitoring time elapses, the PID
function block changes from the ROUT block mode to the block mode selected by means of
the SHED_OPT parameter.
Factory setting:
640000
1
/
32
ms
Resource Block
Parameter Description