Description of device parameters (operating menu) Levelflex FMP51, FMP52, FMP54
140 Endress+Hauser
Navigation
Setup ® Advanced setup ® Linearization ® Table mode
Condition
Only visible if the "Table" linearization type has been selected.
Description
Defines the method used to enter linearization points into the table.
Selection
• Manual
The level and the associated linearized value are entered manually for each linearization point.
•
Semi-automatic
The level is measured by the device for each linearization point. The associated linearized value
is entered manually.
• Clear table
Deletes the existing linearization table.
• Sort table
Rearranges the linerization points into an ascending order.
Factory setting
Manual
Additional information
Conditions the linearization table must meet:
• The table may consist of up to 32 pairs of values "Level - Linearized Value".
• The table must be monotonic (monotonically increasing or decreasing).
• The first linearization point must refer to the minimum level.
• The last linearization point must refer to the maximum level.
Table number
Navigation
Setup ® Advanced setup ® Linearization ® Table number
Condition
Only visible if the "Table" linearization type has been selected.
Description
Index of the linearization point which is entered in the subsequent parameters.
Input range
1 ... 32
Factory setting
1
Level
Navigation
Setup ® Advanced setup ® Linearization ® Level
Condition
Only visible if the "Table" linearization type has been selected.
Description
Definition or display of the (unlinearized) level of the respective linearization point.
Input range
Depending on the parametrized measuring range. See the parameters Empty calibration
(® ä 119) and Full calibration (® ä 120).
Factory setting
0