EasyManua.ls Logo

Endress+Hauser Liquicap M FMI51 HART - Function: Safety Settings; Function: Output on Alarm

Endress+Hauser Liquicap M FMI51 HART
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning Liquicap M FMI51 HART
54 Endress+Hauser
7.4.5 Function: "Safety settings"
Subfunction: "Operating mode"
The "Standard" or "SIL/WHG" operating mode entered is displayed here.
Subfunction: "Output damping"
The output damping entered is displayed here.
Subfunction: "Value empty"
The capacitance of the empty calibration is displayed here.
Subfunction: "Value full"
The capacitance of the full calibration is displayed here.
Subfunction: "Parameter okay"
With this subfunction, you confirm that the parameter values displayed under the "Safety
settings II" function are correct.
The "Parameter okay" subfunction has to be confirmed with "Yes" so the device can be
locked for the SIL/WHG operating mode. In addition, the SIL/WHG function value has
to be selected for the "Operating mode" subfunction and "Locked" must be set for the
"Status" subfunction. The device can be unlocked using the special release code. The
release code is "7452".
7.4.6 Function: "Output on alarm"
Subfunction: "Output"
This function determines the value the output in question assumes when an alarm
condition occurs.
Options:
Max
22 mA
Hold
the last value is retained
User-spec.
as defined in the "Output value" subfunction
t
[mA]
22
t
[mA]
22
3.8
t
[mA]
22
A
C
B
A0040524
A Output current flow in "Max" setting
B Output current flow in "Hold" setting
C Output current flow in "User spec." setting

Table of Contents