Liquicap M FMI51 HART Commissioning
Endress+Hauser 63
7.6.1 Submenu: "Extended calibr."
Function: "Extended calibr."
In this function, you can specify the measuring range.
Subfunction: "Measuring range"
Specify the measuring range in this subfunction.
• C
A
= 0 to 2 000 pF for probe length < 6 m (20 ft)
• C
A
= 0 to 4 000 pF for probe length > 6 m (20 ft)
At the factory, the measuring range is always calibrated to the probe length ordered.
If the electronic insert is used in another probe, the measuring range must be
configured in accordance with the probe length.
Function: "Output/Calculat."
Subfunction: "Sensor DAT stat."
This subfunction shows the status of the sensor DAT.
• OK - sensor DAT is ready for use
• Error - sensor DAT is not ready for use or missing
Subfunction: "Sensor DAT"
Calibration values can be transmitted with this function. A distinction is made between
two types:
• the sensor has been replaced and the electronic insert should continue to be used
• the electronic insert has been replaced but the sensor should continue to be used
For these instances, the calibration values already set can be transferred from the sensor
to the electronic insert or from the electronic insert to the sensor.
Upload
To transfer the calibration values from the sensor to the electronic insert.
Download
To transfer the calibration values from the electronic insert to the sensor.
Subfunction: "Curr. turn down"
This subfunction is not available for "Current span", "Fix. curr. HART".
This function can switch on the current turn down. The current output refers only to a
freely definable part of the measuring range. This is then magnified when displayed.
Subfunction: "Turn down 4 mA"
This subfunction is available only for "Curr. turn down", "On".
Enter the measured value at which the current should be 4 mA.
Subfunction: "Turn down 20 mA"
This subfunction is available only for "Curr. turn down", "On".
Enter the measured value at which the current should be 20 mA.