Commissioning Liquicap M FMI51 HART
50 Endress+Hauser
7.3.8 Operating mode: "Empty calibration" and function - "Dry" for
"Interface" or "Unknown" medium properties
Subfunction: "Value empty"
This field displays 0% and cannot be edited.
Subfunction: "Cap. empty"
Enter the capacitance value, for example calculated with CapCalc.xls.
Subfunction: "Confirm cal."
Empty calibration must be confirmed with this subfunction.
7.3.9 Operating mode: "Full calibration" and function - "Dry" for
"Interface" or "Unknown" medium properties
Subfunction: "Value full"
This field displays 100% and cannot be edited.
Subfunction: "Cap. full"
Enter the capacitance value, for example calculated with CapCalc.xls.
Subfunction: "Confirm cal."
Empty calibration must be confirmed with this subfunction.
7.3.10 Function: "Output damping"
With this function, you can set the reaction time of your measuring device to changes in
the level. If surfaces are turbulent, a higher output damping should be selected.
7.4 Menu: "Safety setting"
Follow the settings in the "Safety settings" menu.
The factory settings are shown in bold.