Options:
• x
• x.x
• x.xx
• x.xxx
Subfunction: "Sep. character"
Select the separator for displaying decimal numbers.
Options:
• . (dot)
• , (comma)
7.7.2 Submenu: "Diagnosis"
Function: "Actual error"
With this function, you can call up the list of all currently pending errors. The errors are
arranged by priority.
If you select an error, a text field appears with a brief description of the error.
Error code list → 77
Function: "Last error"
With this function, you can call up the list of all rectified errors. The option of resetting the
error list with "Reset error list" is also available. It overwrites the last three error codes with
0.
Function: "Password / reset"
This function restores the factory settings. All parameters are reset to factory settings.
Subfunction: "Reset"
The factory settings are bold in the menu overview.
Enter the reset code "333" or "7864" to reset all the parameters to the factory settings.
During a "333" reset, linearization is reset to "linear". However, any linearization table
available is retained and can be activated again where necessary.
During a "7864" reset, linearization is reset to "linear" and the linearization table is deleted.
The subfunctions are also reset:
• "Electronic temp."
• "Max. temp."
• "Max. capacity val."
• "Min. capacity val."
• "Min/Max capacity"
Function: "Electronic temp."
This function displays the temperature measured by the electronic insert.
Subfunction: "Electronic temp."
The subfunction displays the current electronics temperature.
Subfunction: "Max. temp."
The subfunction displays the highest temperature value measured by the device.