Liquicap M FMI51 HART Commissioning
Endress+Hauser 71
Subfunction: "Software version"
This subfunction displays the software version of the device that was assigned in the
factory.
Subfunction: "DD version"
This function indicates the DD version with which this device can be operated using
FieldCare.
Subfunction: "Working hour"
This subfunction displays the number of operating hours.
Subfunction: "Current run time"
This subfunction displays the "current run time" of the device. The first three digits display
the number of days, followed by "d". The next two digits display the hours, followed by "h".
The last two digits indicate the minutes. This subfunction displays the "current run time" of
the device. The first three digits display the number of days, followed by "d". The next two
digits display the hours, followed by "h". The last two digits indicate the minutes.
Function: "Probe length"
In this function, more probe information can be displayed.
Subfunction: "Probe length"
You can read the current probe length in this subfunction.
Probe length (L1) = A – (thread length – plug)
More information are provided →  48.
Subfunction: "Sensitivity"
You can read off the current sensitivity in mm/pF in this subfunction.
7.8 Operation
After Basic setup, Liquicap M outputs the measured value via:
the display and operating module
the current output
20)
the digital HART signal
7.9 FieldCare: operating program from Endress+Hauser
The FieldCare operating program is Endress+Hauser plant asset management tool based
on FDT technology. It is possible to use FieldCare to configure all Endress+Hauser devices
as well as third-party devices which support the FDT standard. The following operating
systems are supported:
Windows 7 Professional SP1 (x32+x64)
Windows 7 Ultimate SP1 (x32+x64)
Windows 7 Enterprise SP1 (x32+x64)
Windows Server 2008 R2 SP2
Windows 8.1
Windows 8.1 Professional
Windows 8.1 Enterprise
Windows 10 Professional
Windows 10 Enterprise
20) The entire measuring range (0 to 100 %) is then mapped to the range (4 to 20 mA) of the current output.