Commissioning Liquicap M FMI51 HART
60 Endress+Hauser
A0040563
A Filled area
B Empty area
Subfunction: "Simulation"
In this subfunction, you can simulate the level or the volume by entering a level under "Sim.
level value" or a volume under "Sim. vol. value".
Subfunction: "Sim. level value" or "Sim. vol. value"
In this subfunction, you can enter the level or volume value to be simulated.
7.5.2 Function: "Linearization"
Subfunction: "Customer unit"
In this subfunction, enter the desired unit for the linearized values, for example: kg, m
3
,
ft
3
.
Subfunction: "Customized text"
In this subfunction, enter your specific name for the unit. The measured value indicated in
the main screen will then be displayed in this unit.
Subfunction: "Diameter"
In this subfunction, specify the diameter of the horizontal cylindrical tank or the spherical
tank. Subfunction is available only for the "dry" type of basic setup.
Subfunction: "Intermed. height"
In this function, specify the intermediate height H ( → 57) of the container in
question. The probe length L1 must be entered here in the event of a wet calibration.
Subfunction: "Edit"
Use this function to enter, modify or read the linearization table.
The following options are available: