Liquicap M FMI51 HART Commissioning
Endress+Hauser 55
Subfunction: "Output value" - only for "Output" and "User-specific"
In this function, specify the user-specific value the current output should assume in an
alarm condition.
Value range: 3.8 to 22 mA.
7.4.7 Function: "Proof test" - self-test
From version FW: V 01.03.00:
before and after the automatic proof test, it is essential to check whether the level
value displayed corresponds to the actual level value
after the self-test, the device automatically returns to the operating mode
Subfunction: "Proof test"
With this subfunction, you activate the device self-test. All electronic components relevant
to the function are tested. Within 40 s, the current output goes through the range of
4 to 22 mA.
7.5 Menu: "Linearization"
"Linearization" is used for converting the level to any unit. You can determine the volume or
the mass in a tank of any shape. Liquicap M makes various linearization modes available
for situations that occur frequently. Furthermore, a linearization table can be entered for
tanks and containers of any shape.
The number and type of subfunctions depend on the type of linearization selected.
Only the "Type" and "Mode" subfunctions are always available.
You can make the following settings in the "Linearization" menu.
The factory settings are shown in bold.