Function: Output / Calculat.
Subfunction: "Current span"
In this subfunction, select the current span to which the measuring range should be
mapped.
Options:
4 to 20 mA
the measuring range 0 to 100 % is mapped to the 4 to 20 mA current span
Fix. curr. HART
a fixed current is an output. Its value can be specified in the "mA value" subfunction. The
measured value is only transmitted via the HART signal
[mA]
[mA]
20
20
4
–10
A B
3.8
%
%
00
C
A0040574
A Current span = 4 to 20 mA.
B Current span = fix. curr. HART.
C mA value
7.6.3 Menu: "Simulation"
Function: "Simulation"
Subfunction: "Simulation"
This function switches on or off the simulation of output current.
Options:
Off
The device is not in the simulation mode. The device is in the measuring mode.
On
The device is in the simulation mode. A measured value is not output. Instead, the
current output assumes the value defined in the "Simulation value" subfunction.
Subfunction: "Simulation value" - only for "Simulation On" mode
Specify the current value to be simulated in this function.
7.7 Menu: "Device properties"
The factory settings are shown in bold.
You can configure the following settings in the "Device properties" menu: