Commissioning Liquicap M FMI51 HART
72 Endress+Hauser
FieldCare supports the following functions:
• configuration of transmitters in online operation
• tank linearization
• loading and saving device data by upload and download
• documentation of the measuring point
Connection options:
HART via Commubox FXA195 and the USB port of a computer.
After reinstalling FieldCare, or by clicking a link in the Help menu, a video can be
activated that explains the possible applications of the program in just a few minutes.
7.9.1 FieldCare
Function scope
FDT-based plant asset management tool from Endress+Hauser. It can configure all smart
field devices in a system and helps you manage them. By using the status information, it is
also a simple but effective way of checking their status and condition.
For additional information about FieldCare, see Operating Instructions BA00027S
and BA00059S
Connection options: HART via Commubox FXA195 and the USB port of a computer
Source for device description files
• www.endress.com → Downloads
• CD–ROM (contact Endress+Hauser)
• DVD (contact Endress+Hauser)
7.9.2 Interface measurement
If there are different media in the container like water and oil, the capacitance values for
"Empty calibration" and "Full calibration" can be calculated.
CapCalc.xls is a capacitance calculation program in FieldCare which can be used to
calculate the calibration values for level measurement and interface measurement.
A0040616
1 Noncoductive medium < 1 µS/cm, DC < 5
2 Emulsion
3 Conductive medium ≥100 µS/cm
The program calculates the calibration values on the basis of the entered data. The secure
functioning of interface measurement can already be determined at this time. The