Liquicap M FMI51 HART Commissioning
Endress+Hauser 51
Safety settings
function: Safety settings
subfunction: Code
- 100
subfunction: Status
- Unlocked
- Locked
function: Safety settings
subfunction: Operating mode
- Standard
- SIL/WHG
subfunction: Output damping
- 1 s
subfunction: Output 1
- MAX
subfunction: Parameter okay
- no
- Yes
function: Safety settings
subfunction: Cap. empty
- x.xx pF
subfunction: Value empty
- x.xxx%
subfunction: Cap. full
- 2 000 pF
subfunction: Value full
- 100.000%
subfunction: Parameter okay
- no
- Yes
function: Operating mode
subfunction: Operating mode
- Standard
- SIL/WHG
subfunction: SIL op. mode
8)
- Unlocked
- Locked
subfunction: Status
- Unlocked
- Locked
function: Output on alarm
subfunction: Output
- Max
- Hold
- User-spec.
subfunction: Output value
9)
- xx.xx mA
function: Proof test
subfunction: Proof test
- Off
- On
8) The subfunction is displayed if the "SIL/WHG" option was selected under the "Operating mode" subfunction.
9) The subfunction is displayed if the "User-specific" option was selected under the "Output" subfunction.