Proline Prowirl 73 Description of device functions
Endress+Hauser 121
SIMULATION
CURRENT
Description
Activates simulation of the current output.
• The notice message #611 "SIMULATION CURRENT OUTPUT" (ä 67) indicates
that simulation is active.
• The value which should be output at the current output is defined in the VALUE
SIMULATION CURRENT function (ä 121).
• The measuring device continues to measure while simulation is in progress, i.e. the
current measured values are output correctly via the other outputs and the display.
!
Note!
The setting is not saved if the power supply fails.
Options
OFF
ON
Factory setting
OFF
VALUE SIMULATION
CURRENT
Prerequisite
The function is only available if ON was selected in the SIMULATION CURRENT
function (ä 121).
Description
Use this function to define an arbitrary value (e.g. 12 mA) to be output at the current
output. This value is used to test downstream devices and the measuring device itself.
!
Note!
The setting is not saved if the power supply fails.
Procedure
• Simulation is started by confirming the simulation value with the
F
key.
•If the
F
key is pressed again afterwards, the prompt "End simulation" (NO/YES)
appears.
• If you choose "NO", simulation remains active and the group selection is called up.
The simulation can be switched off again via the SIMULATION CURRENT function.
• If you choose "YES", you end the simulation and the group selection is called up.
User input
Floating-point number: 3.60 to 22.60 mA
Factory setting
3.60 mA
Function description, CURRENT OUTPUT group