NAV IP Access controller
106
DoorLocation:Descriptionofthedoorlocation.
DoorUnlockTime:SetthedooropentimewhenavalidcardisswipedortheRequest
toExitbuttonispressed.ThedoorremainsopenaslongastheRTXbuttonispressed
down.Thedooropentimedoesnotcountuntilthebuttonisreleased.Iftwocardsare
swipedsuccessively,thedooropentimedoesnotcountuntilthesecondcardhas
beenswiped.Thedefaulttimeis3seconds.Themaximaldooropentimeis59999
seconds.
DoorHeldOpenTime:Doorsensormonitorstheopen/closestatusofadoor.If
“unlock”isnotsetbythesystem(doorisnormallyconsideredclosed),thendoor
shouldcloseafteropening.Itisconsideredabnormalifcontrollerdoesnotreceivethe
doorclosesignalfromdoorsensorforareasonableamountoftimeafterthedooris
opened.Thistimeperiodiscalldoorheldopentimeordoorovertime.Accordingto
thissetting,thecontrollerwilldeterminewhethertogenerateanalarmornotafter
thedoorsensortimeouts.Thedefaultvalueofdoorheldopentimeis5seconds.The
maximaldoorheldopentimeis59999seconds.
Steps:
1) Selectthedoorpage.
2) Clickthedoorwhichneedstobeset.
3) Inputdoorinformationincluding:doorlocation,unlockduration,heldopen
duration,interlocketc.Iftwoormoredoorsareinterlocked,theycannotbe
openedthesametime.Ifoneoftheinterlockeddoorsisopen,theotherdoors
cannotbeopeneduntilthefirstdoorisclosed.Inshort,therecanbeonlyone
dooropenatanytimepointamonginterlockeddoors.Usercansetinterlock
functionwhenaninterlockcompatiblecontrollercontrolstwoormoredoors.This
settingisparticularlysuitabletoenvironmentthatrequireshighlevelsecurity,
suchasbanksandprisons.
4) Clickthe“Savebuttontosaveyourchanges.
12.1.5.2 Reader
Settingspageforthereadernumber,name,doorlocation,keypadreader,systemreader,inputtimefor
keypad,in/outtype,sourceanddestinationareaetc.