B680H 30 732719 - Rev.E
Translation of the original instructions
ENGLISH
3 Basic programming
Basic function Default
][
Simply Connect
0 disabled
1 enabled
2 , 3 , 4 not used
0
cF
BARRIER CONFIGURATION
01…06 (levels)
06
i
To establish this value, refer to § 5.2. Setting a default
value that is lower than the one actually installed can
cause irreversible damage to the beam and to the struc-
ture of the barrier. Loading a different configuration will
reset the parameters to the default values.
dF
DEFAULT CONFIGURATION
Displays Y if the programming corresponds to the
default settings. Select Y if you wish to reload
the default values.
Y the programming corresponds to the
DEFAULT settings
no the programming does NOT correspond to
the default settings
Y
Ct
OPPOSING BARRIER CONFIGURATION
Configure the board as Primary or Secondary.
MA Primary
SL Secondary
MA
i
The following parameters are not displayed on the
Secondary board SC-bu-LO-PA-L1-L2-tL-PF-
tP-t (for further information see § 8.1).
bu
BUS 2easy DEVICE LEARNING
See the relative section.
no
LO
FUNCTIONING LOGIC
E
A Automatic
A1 Automatic 1
E Semi-automatic
P Car park\
PA Automatic Parking
Cn Condominium
CA Automatic condominium
C Hold-to-run
CU Custom (logic created
in expert programming
mode)
i
Parameter CU is only displayed if a modification has
been made to the advanced programming parameters.
PA
PAUSE TIME
00…59 Adjustment step: 1 s
1.0…4.1 Adjustment step: 10 s
20
So
OPENING SPEED
01…10 (minimum speed ... maximum speed)
10
Basic function Default
Sc
CLOSING SPEED
01…10 (minimum speed ... maximum speed)
*The default value varies according to the setting
of cF:
10 if cF=01
05 if cF=02 or 03
04 if cF=04
02 if cF=05 or 06
02
*
i
Setting an excessive speed can cause irreversible damage
to the beam and to the structure of the barrier.
L1
LOOP1
Loop connected to input LOOP1 (OPEN function).
Y LOOP1 enabled
no LOOP1 not enabled
no
L2
LOOP2
Loop connected to input LOOP2 (SAFETY/ CLOSE
function).
Y LOOP2 enabled
no LOOP2 not enabled
no
S1
Sensitivity LOOP1
Regulates the sensitivity of the vehicle detection
loop
00...10 (sensitivity levels, 10 = maximum
sensitivity)
05
S2
Sensitivity LOOP2
Regulates the sensitivity of the vehicle detection
loop
00...10 (sensitivity levels, 10 = maximum
sensitivity)
05
Mt
MOTOR OPERATION IN DEAD MAN MODE
++ OPENS (displaying oP) as long as the button
remains pressed.
--
CLOSES (displaying cL) as long as the button
remains pressed.
--
tL
SETUP
Acquire the limit switch positions. See the
relative section.
--