SEMIAUTOMATIC LOGICS
In all semi-automatic logics, the OPEN command:
- with the beam closed, it commands the opening
- during closing, it reverses to open
■
E Semi-automatic E
OPEN command:
- during opening, it stops the movement
- when open, it closes the automation
If LOOP1 is triggered:
- with the beam closed, it commands the opening
- during closing, it reverses to open
If the Photocell / LOOP2 is triggered:
- during closing, it reverses to open
■
P - Car park
If LOOP1 is triggered:
- with the beam closed, it commands the open-
ing. When the movement has ended and when
released, it closes the automation
- during closing, it reverses to open. When the
movement has ended and when released, it closes
the automation
If the Photocell / LOOP2 is triggered:
- during closing, it stops the movement. When
released, it continues to close
■
Cn - Condominium
If the Photocell is triggered:
- during closing, it reverses to open and closes again
after the pause time
If LOOP1 is triggered:
- with the beam closed, it commands the opening
- reverse to open during closing
If LOOP2 is triggered:
- during opening, when the movement has ended
and when released, it closes the automation
- during closing, it reverses to open. When the
movement has ended and when released, it closes
the automation
DEAD MAN LOGIC MAINTAINED
■ C - Dead-man
Logic
C requires the use of maintained OPEN and
CLOSE commands.
The control must be activated intentionally and the
barrier must be visible.
- Maintained OPEN opens the automation
- Maintained CLOSE closes the automation
If photocells LOOP1 and LOOP2 are triggered:
- during closing, they stop the movement
CUSTOM LOGIC
i
Custom logic is created in expert programming mode.
Read the relevant section carefully before making
changes at this level.