B680H 56 732719 - Rev.E
3 4 5 6 7 8 9
11
10
OP-A
CLOSE
STOP
EMR
+24 V
+24 V
+24 V
+24 V
+24 V
FSW
GND
GND
+24 V
OUT1
OUT2
OUT3
Relay NO
Relay COM
GND
12 13 14 15 16 17 18 19 2120
3 4 5 6 7 8 9
11
10
OP-A
CLOSE
STOP
EMR
+24 V
+24 V
+24 V
+24 V
+24 V
FSW
GND
GND
+24 V
OUT1
OUT2
OUT3
Relay NO
Relay COM
GND
12 13 14 15 16 17 18 19 2120
B680H 1
B680H 1
B680H 2
B680H 2
Translation of the original instructions
ENGLISH
8.2 TWO INTERLOCKED BARRIERS
This configuration allows two barriers to be controlled
where the opening of one is subject to the closing of
the other.
The barriers are both Primary.
INTERLOCK CONFIGURATION
1. Connect the two barriers as per 39
2. In advanced programming program both boards
with o1=18 and P1=no.
3. Carry out the start up and setup procedure