2. Commissioning
2-38
Festo Festo P .BE CP FB13-E-EN en 9910c
2.3.2 Send parametrizing data
The parametrizing data are transferred from the DP master to
the CP system with the function Set_Prm.
Octet 1: Station status
Bit Meaning Explanation
0 Reserved
1
2
3 WD_On Response monitoring of t he CP system on/off:
log. 0:off
log. 1:on
4 Freeze_Req log. 0: Freeze mode not requested by the master
log. 1: Freeze mode set by the master
5 Sync_Req log. 0: Sync mode not requested by the master
log. 1: Sync mode set by the master
6 Unlock_Req Bit 7 Bit 6 Explanation
7 Lock_Req
0 0 min T
SDR
+ CP system parameter
may be overwritten
0 1 CP system released for other
masters
1 0 CP system released for other
masters
1 1 CP system released for other
masters